background image

1315-00

Page 6

60707-123

INSTALLING THE FUEL LINE

DANGER:  PERSONAL INJURY

Units that are intended to be run unattended MUST
have an electric fuel solenoid installed. This solenoid
MUST be wired to AUTOMATICALLY turn off the fuel
whenever the engine stops.

Unit location will determine the size of fuel line that is

required to supply the engine with a constant fuel pressure.

Refer to the tables below for fuel line size, and recommended

tank size.  For distances of 100 feet and over, a two regulator

fuel system is recommended. This system consisting of a

primary 10-15# regulator at the tank and a 6 ounce

secondary regulator installed about 10 feet from the

generator. You need to run a 3/4 inch line or larger from the

secondary regulator to the engine-generator set.  When a two

(2) regulator fuel system is used, a fuel line size of 3/8 inch is

generally adequate for distances up to 300 feet.  The line

size from the table below applies to the distance from the

second regulator to the demand regulator.  

A positive fuel

shut-off device must be installed in the fuel line close to
the engine generator set.  

This may be either a lockable

manual shut-off valve available from your local fuel installer,

or a 12 volt DC fuel solenoid valve.  This optional 12 volt DC

valve is available through your local Winco dealer.

The fuel line used to connect the supply line to the demand

regulator must be a locally approved flexible fuel line.

Products used will vary in different regions depending on

availability and local codes.  Consult with your local fuel

supplier to insure complete compliance with ALL codes.

1. Remove the pipe plug from the demand regulator.

2. Connect the flex fuel line to the demand regulator to

the optional fuel solenoid..

DANGER: PERSONAL INJURY

Do not use galvanized pipe in the fuel line runs. The
galvanized coating will become eroded and flake off,
causing possible obstruction or damage to the
regulator or fuel valve. The obstruction could cause  an
inoperative engine or an explosive fuel leak.

Size of pipe required for generators operating on natural gas/

LP gas.

Length of Fuel Line*

    Fuel Line Size

  less than 25 feet

3/4 inch black pipe

  25 to 100 feet

 1 inch black pipe

  over 100 feet

not  recommended**

*allow an additional 3 feet for each standard elbow.  Do not

use ‘street ells’ (restrictive)

** Consult factory for fuel runs over 100 feet.

DANGER! - FIRE - PERSONAL INJURY -

Be careful when sealing gas joints. Excessive sealing
compound can be drawn into the solenoid, regulator or
carburetor causing an engine malfunction or dangerous
fuel leak.

FUEL PRESSURE

Correct fuel pressure cannot be stressed enough.  The most

common cause for inoperative systems is an inadequate or

incorrect fuel pressure.  Power and performance of the

engine is in direct relation to the correctness of the fuel

system.  Shown below is a block diagram of a typical L.P.

or N.G. installation.

Reference numbers 1 through 3 in the block diagrams

above are system parts supplied by customer.

Reference number 4 is the engine generator set.
Below is a table of the fuel pressure reading at each

reference in the system.

Fuel Pressure Table

Single Regulator (L.P. Vapor only)

       1

     3               4

UNIT OFF

TANK PSI 7-11 in

7-11 in

4-6 oz

4-6 oz

STARTING TANK PSI 7-11 in

7-11 in

4-6 oz

4-6 oz

NO LOAD

TANK PSI 7-11 in

7-11 in

4-6 oz

4-6 oz

FULL LOAD TANK PSI 7-11 in

7-11 in

4-6 oz

4-6 oz

Two (2) Regulator System (L.P. Vapor only)

       1

      2

       3

  4

UNIT OFF

TANK PSI 10-15 lbs 7-11 in

7-11 in

4-6 oz

4-6 oz

STARTING TANK PSI 10-15 lbs 7-11 in

7-11 in

4-6 oz

4-6 oz

NO LOAD

TANK PSI 10-15 lbs 7-11 in

7-11 in

4-6 oz

4-6 oz

FULL LOAD TANK PSI 10-15 lbs 7-11 in

7-11 in

4-6 oz

4-6 oz

Содержание HPS12000HE/E

Страница 1: ...INSTALLATION OPERATION and MAINTENANCE INSTRUCTIONS TRI FUEL PORTABLE GENERATORS OWNERS MANUAL HPS9000VE MODELS HPS6000HE H HPS9000VE D HPS12000HE E HPS6000HE HPS12000HE ...

Страница 2: ...L NUMBER HERE No other HOME POWER generator has the same serial number as yours It is important that you record the number and other vital information here If you should ever need to contact us on this unit it will help us to respond to your needs faster MODEL______________________________________ SERIAL NUMBER _____________________________ PURCHASEDATE_____________________________ DEALER_________...

Страница 3: ...fuels always present a hazard of possible explosion and or fire a Do not refuel when the engine is running or hot Allow the engine to cool at least two minutes before refueling b Keep fuel containers out of reach of children c Do not smoke or use open flame near the generator set or fuel tank d Keep a fire extinguisher nearby and know its proper use Fire extinguishers rated ABC by NFPA are appropr...

Страница 4: ... damage to the engine generator set DO NOT install and operate these portable generators in a small compartment i e generator compartment of vehicles motor homes or travel trailers These compartments will not allow enough free flow fresh air to reach the engine generator set for cooling and will cause the unit to overheat damaging both the engine and the generator Small compartments will also deve...

Страница 5: ...minutes to insure that the unit you have received is the correct model and review the specification pages in this manual to insure that this unit fits your job requirements 3 After removing the engine generator from the carton locate and remove the shipping strap attached to the generator shock mount See attached tag for removal instructions UNIT CAPABILITIES Generator Connections The diagram belo...

Страница 6: ...thout a battery on gasoline only Installation and servicing of batteries must be performed or supervised only by personnel knowledgeable of batteries and the required precautions Keep unauthorized personnel away from batteries When installing or replacing batteries use the proper group size starting battery The battery should be a Maintenance Free lead acid design Deep cycle batteries will not wor...

Страница 7: ... the engine the engine switch will remain in the ON position GASOLINE FUEL When using gasoline always use a good grade of unleaded fuel Leaded gasoline may be used if unleaded is not available Gasoline containing alcohol such as gasohol is not recommended However if gasoline with Ethanol is used it must not contain more than 10 percent Ethanol and must be removed from the engine during storage DO ...

Страница 8: ... optional fuel solenoid DANGER PERSONAL INJURY Do not use galvanized pipe in the fuel line runs The galvanized coating will become eroded and flake off causing possible obstruction or damage to the regulator or fuel valve The obstruction could cause an inoperative engine or an explosive fuel leak Size of pipe required for generators operating on natural gas LP gas Length of Fuel Line Fuel Line Siz...

Страница 9: ... the demand regulator 4 Reinstall the plastic plug in the regulator 5 Check to be sure the gasoline fuel valve is off 6 Fill the gasoline fuel tank 7 Turn on the gasoline fuel valve 8 Start the engine Optional Dolly Kit HPS9000 HPS6000 An optional dolly kit is available for these engine generator sets The dolly kit comes with instructions and parts list After installing the dolly kit file the inst...

Страница 10: ...l with fresh oil d Remove the spark plug pour approximately 1 2 ounce 15 cc of engine oil into the cylinder and crank slowly to distribute oil Replace spark plug e Clean dirt and chaff from cylinder cylinder head fins blower housing rotating screen and muffler areas f Store in a clean and dry area OPERATING SPEED The engine generator must be run at the correct speed in order to produce the proper ...

Страница 11: ...d local codes and regulations Check with local authorities before proceeding These generators come equipped with a 4 wire 120 240 volt receptacle designed to power both 120 and 240 volt loads There are 2 hots a neutral and a ground wire connection in the 4 wire 120 240 volt receptacle L14 30R This receptacle is protected by a double pole circuit breaker rated for generator output Below is a table ...

Страница 12: ...r every 25 hours whichever occurs first Service more often if necessary Clean by tapping gently on flat surface If very dirty replace the cartridge using only original equipment parts available at any engine service center Do not use petroleum solvents such as kerosene to attempt to clean the cartridge They may cause deterioration of the cartridge DO NOT OIL CARTRIDGE DO NOT USE PRESSURIZED AIR TO...

Страница 13: ...be removed every 50 hours for cleaning and inspection Replace if damaged TROUBLESHOOTING HINTS PROBLEM SYMPTOMS POSSIBLE CAUSES Won t Start Low Oil Level Fouled spark plug Out of fuel Stop switch in stop position Wrong fuel pressure Fuel is shut off Runs rough Wrong fuel pressure Not enough fuel volume Fuel mixture not properly adjusted Gasoline carburetor gummed up Fuel filter plugged ___________...

Страница 14: ...1315 00 Page 12 60707 123 DATE ITEM WORK PERFORMED ...

Страница 15: ...enter Minnesota THERE IS NO OTHER EXPRESS WARRANTY To the extent permitted by law any and all warranties including those of merchantability and fitness for a particu lar purpose are limited to 12 months or 1000 hours which ever accurs first from date of purchase In no event is WINCO liable for incidental or consequential damages Note Some states do not allow limitation on the duration of implied w...

Страница 16: ...225 S Cordova Ave LeCenter Mn 56057 60707 123 1315 00 ...

Отзывы: