HLP-P  Inverters

one inverter in the same enclosure so that the temperature inside the 

enclosure be kept below 40

 to avoid overheat or the risk of fire. 

  Be  sure  to  turn  off  the  power  supply  before  dissembling  or 

assembling the operation keypanel and fixing the front cover to avoid 

bad contact causing faults or non-display of the operator. 

  Do not install the inverter in a space with explosive gas to avoid the 

risk of explosion.

  If the inverter is used at or above 1000m above seal level, the cooling 

efficiency will be worse, so please run it by de-rating.

  Do not install any contactor and other components of capacitor or 

varistor on the output side of the inverter. Otherwise it will cause 

malfunctions and damages of components of the inverter.

  Do not install any switch component like air circuit breaker or 

contactor at the output of the inverter. If any of such components 

must be installed because of the requirements of process and 

others, it must be ensured that the inverter has no output when the 

switch acts. In addition, it is forbidden to install any capacitor for 

improvement of power factor or any varistor against thunder at the 

output. Otherwise it will cause malfunctions, tripping protection 

and damages of components of the inverter. Please remove them as 

shown in the below diagram.

  It will affect the service life of the inverter if a contact is connected 

to the front end of input of the inverter to control its starts and stops. 

Generally it is required to control it through FOR or REV terminals. 

Special attention should be paid to its use in the case of frequent 

starts and stops.

  Please use an independent power supply for the inverter. Do avoid 

using the common power supply with an electrical welder and other 

equipment with strong disturbance. Otherwise it will cause the 

protection or even damage of the inverter.

Inverter

Содержание HLP-P Series

Страница 1: ......

Страница 2: ......

Страница 3: ......

Страница 4: ...and Specifications 7 1 Particular Specifications 7 2 General Specifications 8 Storage and Installation 10 1 Storage 10 2 Installation Site and Environment 10 3 Installation and Direction 10 Wiring 12...

Страница 5: ...nd Troubleshooting 83 1 Precautions about Inspection and Maintenance 83 2 Periodical Inspection and Maintenance items 83 3 Fault Indication and Troubleshooting 84 4 Faults and Analysis 86 Selection of...

Страница 6: ...formance Please read carefully the operation manual before putting the inverter to use so as to correctly install and operate the inverter give full play to its functions and ensure the safety Please...

Страница 7: ...rious factors during the transportation special attention should be paid to the following points before the assembly and installation If there is anything abnormal please notify the dealer or the rele...

Страница 8: ...3PH380V17 5A7 5KW Freq Range 0 1 400Hz HOLIP ELECTRONICS CO LTD Model HLP P 07D5 43 B Hardware Version Voltage Rating 43 means 3 phase 380V Inverter Capacity 07D5 means 7 5KW Serial No P means P serie...

Страница 9: ...erminal of E must be grounded separately and never connected to line zero Otherwise it will easily cause the protection or errors of the inverter Caution Do not carry the front cover of the inverter d...

Страница 10: ...or at the output of the inverter If any of such components must be installed because of the requirements of process and others it must be ensured that the inverter has no output when the switch acts I...

Отзывы: