background image

HOLDPEAK

870L

 

OPERATION MANUAL 

This LCD Auto Range & Auto Power off Digital AC clamp multi 

meter is a portable, 3 3/4-digit multi meter. It is ideally suited for 
field, laboratory, shop and home applications. 

1. SAFETY INFORMATION

The  following  safety  information  must  be  observed  to  in  sure 
maximum personal safety during the operation at this meter. 
1) When  measuring  voltage  ensure  that  instrument  is  not
switched  to  the  current  range,  resistance  range,  diode  and 
continuity range, capacitance range or temperature range. 
2) Use  extreme  care  when  measuring  voltage  above  50V.
especially    from sources where high energy is existed. 
3) Avoid making connections to "live" circuits whenever possible
Before making resistance measurements, diode or continuity test, 
capacitance test or temperature test, ensure that the circuit under 
test is de-energized. 
4) Always ensure that the correct function and range is selected.
5) Extreme  care  should  be  taken  when  using  the  instrument  to
conjunction with a current transformer connected to the terminals 
if an open circuit occurs. 
6) Ensure  that  the  test  leads  and  probes  are  in  good  condition
with no damage to the insulation. 
7) Take  care  not  to  exceed  the  over-load  limits  as  given  in  the
specifications. 
8) Before  opening  the  cover  of  the  battery  cabinet  to  replace
batteries. disconnect the test leads from    any external circuit, set 
the selector switch to    "OFF" position. 
9) Keep  the  fingers  after  the  protection  ring  when  measuring
through the instrument lead. 
10) In order to avoid incorrect data, when the battery is low, they
have to replace the battery 

2. Panel Layout

1

Rotary Switch: use this switch to select functions and ranges 

 

2

D.HOLD key

In any range, push the key, the present display 

value will be locked and the "H " symbol will appear, push it again 
to exit HOLD and the " H" symbol disappear. 

3

SELECT key

This tester turn 

on the "Ω" range. Push the key 

to choose resistance, diode ,continuity or capacitance test. This 
tester turn    on the voltage or current range, Push 

“SELECT” to 

choose AC or DC test. This tester turn on the 

/

” range press 

this button, select 

/

measurement; 

4

REL key

Push the key, the present display value will be stored 

in memory ,then the new display value is the difference between 
input value and stored data. In Hz/Duty measurement, it can not 
work. Press this button the screen will also shows that "

symbol   

5)

Maximum / minimum measurement: Push this key ,the

instrument enter into the model, dynamic record in change input 
signal to capture and record in the maximum signal (MAX) or 
minimum value (MIN) 

6

Hz/DUTY key

In Hz range, push the key, you can measure the 

duty ,push again, go back to    Hz    measurement. In AC voltage 
or AC current range, push it, you can measure Hz and duty, but 
the measurement range will be smaller, and the auto range mode 
will be changed to manual range mode. 

7

LCD Display

LCD Dual Display, facilitates reads the data. 

8

T+

VΩHz

  Input Jack 

COM    Input Jack

T-

Input Jack

 

2.1 GENERAL SPECIFICATIONS 

Display:    3 3/4 digit LCD with a max. reading of 3999. 
Range control:    Auto range   
Polarity:    Automatic negative polarity indication. 
Zero adjustment: Automatic. 
Over range indication: Only the "OL" or 

“-OL”display. 

Low  battery:  The  "BATT"  is  display  when  the  battery  voltage  is 
below 2.4V approx. 
Auto Power Off: 15 minutes after stopping the switch or no push 
button,  the  meter  automatically  enter  to  power  off  mode.  Push 
button or run switch, auto power off disable. 
Safety Standards: The meter is up to the standards of IEC1010 
Double  Insulation,  Pollution  Degree  2,  Overvoltage  Category 

 

600V. 
Clamp opening size: 45mm. 
Operating Environment: Temperature    0

104

  (0

40

), 

humidity

80%RH. 

Storage Environment: Temperature    -4

140

(-20

60

), 

humidity

80%RH. 

Power supply: 

9V Zinc-carbon battery.

 

Dimension: 225(H)×77(W)×45(D)mm. 
Weight: Approx. 350g (including batteries). 

2.2 ELECTRICAL SPECIFICATIONS 

Accuracies are ±(% of rnumber in last digit) 
at 23

±

5

,

75%RH. 

2.2.1 DC Voltage 

Range 

Accuracy 

Resolution 

400mV 

0.5% of rdg+15digits 

0.1mV 

4V 

1mV 

40V 

10mV 

400V 

100mV 

1000V 

1.2% of rdg+10 digits 

1V 

Overload protection: 1000V DC/750Vrms AC 
Impedance: 10M

Ω,

More than100M

Ω

  on 400mV scale 

2.2.2 AC Voltage 

Range 

Accuracy 

Resolution 

Frequency 

4V 

1.0% of rdg+15 digits 

1mV 

50

400Hz 

40V 

10mV 

400V 

100mV 

750V 

2.5% of rdg+15 digits 

1V 

50

100Hz 

Average sensing, calibrated to rms of sine wave 
Overload protection: 1000V DC/750Vrms AC 
Impedance: 10M

Ω,

More than 100M

Ω

  on 400mV scale 

2.2.3 AC Current 

Range 

Accuracy 

Resolution Frequency 

40A 

3.0% of rdg+20 digits 

0.01A 

50

60Hz 

400A 

2.5% of rdg+20 digits 

0.1A 

1000A 

0

800 

2.5% of rdg+25 digits 

1A 

800

1000 

5.5% of rdg+25 digits 

Average sensing, calibrated to rms of sine wave 
Overload protection: 1000Arms within 60 seconds 

2.2.4 Resistance 

Range 

Accuracy 

Resolution 

400Ω 

1.8% of rdg+20 digits 

0.1Ω 

4k

Ω 

1.2% of rdg+20 digits 

1Ω 

40k

Ω 

10Ω 

400k

Ω 

100Ω 

4MΩ 

1k

Ω 

40MΩ 

2.0% of rdg+20 digits 

10k

Ω 

Overload protection: 250V DC/250Vrms AC 

2.2.5 Capacitance 

Range 

Accuracy 

Resolution 

40nF 

3.5% of rdg+30 digits 

10PF 

400nF 

2.5% of rdg+25 digits 

100PF 

4u

μ

1nF 

40

μ

5.0% of rdg+10 digits 

10nF 

400

μ

20.0% of rdg+20 digits 

100nF 

4000

μ

1

μ

Overload protection: 250V DC/220Vrms AC 

2.2.6 Frequency 

Range 

Accuracy 

Resolution 

Sensitivity 

10Hz 

0.5% of rdg+10 digits 

0.01Hz 

Range of 

input 

voltage:1.5V

~10V,

 

If input 

voltage over 

range, need 

adjust 

100Hz 

0.1Hz 

1000Hz 

1Hz 

10kHz 

10Hz 

100kHz 

100Hz 

1000kHz 

1kHz 

10MHz 

10kHz 

Overload protection: 250V DC/220Vrms AC 

Duty cycle:    0.1%

99.9% 

2.2.7 Temperature(NiCr-NiSi sensor) 

Range 

Accuracy 

Resolution 

/

 

-20

150

 

-4

302

 

±

(3

+2) 

1

/1

 

150

300

 

302

572

 

3.0% of rdg+2 digits 

300

1000

 

572

1832

 

3.5% of rdg+5 digits 

Overload protection: 36V DC/36Vrms AC 