-70
-
TROUBLE SHOOTING
(
O
u
t
door unit)
FAILURE CODE
S
(CHECK
ON
THE WIRED
REMOTE
CONTROLLER)
Faulty defrost sensor Te
Sensor disconnected, or broken, or short circuit
Faulty sensor Tao
Sensor disconnected, or broken, or short circuit
Faulty sensor Ts
Sensor disconnected, or broken, or short circuit
Faulty sensor Td
Sensor disconnected, or broken, or short circuit
Input overcurrent
Over current of the system, or broken of the
current sensor,
or malfunction
of
indoor or
outdoor fan motors, or faulty PCB.
15
16
17
14
19
System high pressure
protection
High pressure switch is disconnected, or high
pressure switch worked, or Tc too high and
faulty outdoor fan motor when cooling, or
faulty indoor fan motors when heating, or
refrigerant
excessive charge
1E
System low pressure
protection
Low pressure switch is disconnected, or low
pressure switch worked, or Te too low and
faulty outdoor fan motors when heating, or
faulty indoor fan motor when cooling, or
refrigerant shortage
1F
IPM protection
IPM over current, or short circuit, or
IPM
temperature
is
too high, or IPM input
voltage too
low,
or faulty SPDU (or ISPM).
EEPROM fault
Faulty outdoor unit PCB
20
21
Overh
eat
protection of
compressor
Serious lack of refrigerant of the system, or
too
high
ambient temperature, or PMVs
is
blocked
22
Over h
eat
protection of SPDU
(or ISPM)
Ambient tem
perature
too high, or outdoor fan
is
blocked, or bad air circulation o
n
outdoor unit
23
DC fan motor fault
Fan is blocked, or the terminal is disconnected from
the PCB
24
POSSIBLE REASONS
Faulty 4-way valve
switching on
Coil of 4-way valve is disconnected, or faulty
outdoor PCB
25
Faulty sensor Tc
Sensor disconnected, or broken, or short circuit
26
Faulty sensor Toci
Sensor disconnected, or broken, or short circuit
2A
Low voltage protection
VDC<194V, too low voltage from power source
High voltage protection
VDC>400V, too high voltage from power source
2C
2D
Abnormal communication
between main PCB and
SPDU
(or ISPM)
2E
Compressor
is
locked
Faulty compressor or SPDU (or ISPM)
Excessive c
ompressor vibration
Faulty compressor
Compressor lose position
Faulty SPDU (or ISPM)
Faulty compressor start
Faulty compressor or SPDU (or ISPM)
Faulty position checking
circuit
Faulty SPDU (or ISPM)
Compressor br
eakdown
Faulty compressor or SPDU (or ISPM)
32
33
34
35
37
38
Communication cables broken, or bad connection,
or faulty main PCB, or faulty SPDU (or ISPM)
Failure code