Modbus Communications 39
HIT-4U
HP-327
Register
(Decimal)
Description
Data
Type
Access Notes
4014
Rate Alarm
High Set Point
FP32
R/W
0.001- Max limited
by rate decimal
point selection:
999.999, 9999.99,
99999.9, 99999
7000
Request Hourly
Log Pointer
FP32
RO
-1 (cleared logs) -
767
7001
Request Daily
Log Pointer
FP32
RO
-1 (cleared logs) -
383
7002
Request Event
Log Pointer
FP32
RO
0-344
7003
Request Date
FP32
RO
010100 - 123199
7004
Request Time
FP32
RO
000000 - 235959
7005
Request Grand
Total
FP64
RO
0 – 99999999
16-bit registers
available at
address 7056-7059
(FP64) and 7062-
7063 (FP32)
7006
Request Rate
FP32
RO
0 – Max limited by
rate decimal point
selection: 999.999,
9999.99, 99999.9,
99999
16-bit registers
available at
address 7050-7051
7007
Request Daily
Total
FP64
RO
0 – 99999999
7008
Request Daily
Run Time
Seconds
FP32
RO
0 – 86400
7009
Request Hourly
Total
FP64
RO
0 – 99999999
7010
Request Hourly
Run Time
Seconds
FP32
RO
0 – 3600
Flow-Tech, Inc. | In MD 410-666-3200 - In VA 804-752-3450 | www.flowtechonline.com