the factory for servicing. Refer to Technical Bulletin HA-97 for cleaning information.
4) When the condition exists as stated in 2) the device needs to be cleaned or returned to
3) In the alarm state both LEDs are on Red continuously.
2) When the sensitivity drifts outside of its sensitivity limits, both LEDs flash Red
SLR -24/-835/SLV-24 AND SOC-24V SERIES SENSITIVITY TEST FEATURE
1) In normal condition both LEDs flash Green.
For go/no-go testing, a magnet will be required.
1. Hold the magnet just UNDER the word "TEST" as shown on Diagram A.
2. The detector should alarm within 10 seconds (If control panel is programmed for Fire Alarm
Verification, it may take up to 30 seconds).
3. The detector's LEDs should be on Red continuously and any control panel indicating appliances should activate.
4. Silence the system and activate the control panel reset to reset smoke detector.
5. The smoke detector LEDs should flash Green.
TESTING THE SLR-835/SLR-24 AND THE SLV-24 SERIES INSTALLATION
FIG. 1
DWG. # HA-06-060
PART# 1700-09987
(Pg.2 of 2, 06/16)
DIAGRAM A
FIG. 2
Hold Magnet
Here
TEST
Testing is performed with the Hochiki America Alarm Test Magnet
SIJ-24/-24C SENSITIVITY TEST PROCEDURE
POWER CONDITIONS MAY AFFECT SENSITIVITY. ALWAYS RESET POWER PRIOR TO
within specified sensitivity limits and may require service. See Tech Bulletin
3). Place magnet on detector as shown in Figure 2 (opposite side).
source and with normal applied power, place magnet as shown in Figure 1.
1). With detector wired to appropriate initiating circuit or current limited power
CONDUCT TESTING ONLY UNDER NORMAL STANDBY CONDITIONS. ABNORMAL OR LOW
produce an alarm when magnet is positioned as in Figure 2, detector is not
5). If detector does alarm when magnet is positioned as in Figure 1 or does not
2). Wait at least six seconds. Detector SHOULD not alarm and LED should not light.
TESTING OF NEXT UNIT.
4). Wait at least six seconds. Detector SHOULD alarm.
HA-97 for more information and for additional sensitivity test devices.
NOTE:
SIJ-24/-24C DETECTOR
TOP VIEW OF
(Part Number 0700-01110) shown below.
TEST DEVICE:
TEST PROCEDURE
TOP VIEW
SIDE VIEW
NS6-100
DEVICE
END OF LINE
LISTED
EXCEPT NS6-100
(EXCEPT NS4-100)
N/A
47mA (75mA @ 18.0V MAX.)
HSC-4R12
LISTED
DEVICE
END OF LINE
2
1 2-WIRE AUXILIARY RELAY BASE
4-WIRE 24V BASE
* - Requires External Current
Limiting To 150mA Max.
2
1
1
ID
HB-5
ALARM CURRENT
43mA (70mA @ 33.0V MAX.)
HB-4
HB-55
HB-4
HB-5
HB-3
HB-55
HB-73
HB-71
N/A
HB-72
1
49mA (62mA @ 30.0V MAX.)
46mA (77mA @ 33.0V MAX.)
150mA @ 15.0~33.0V MAX.
88mA (98mA @ 26.5V MAX.)
43mA (58mA @ 30.0V MAX.)
150mA @ 15.0~33.0V MAX.
46mA (77mA @ 33.0V MAX.)
93mA (136mA @ 33.0V MAX.)
43mA (70mA @ 33.0V MAX.)
43mA (58mA @ 30.0V MAX.)
93mA (136mA @ 33.0V MAX.)
HB-3
AND NS6 ARE IDENTICAL
- BASES WITH THE "W" SUFFIX
ARE WHITE IN COLOR
NS6 SERIES
NOTE: - WIRING TERMINALS FOR THE NS4
BASE
NS6-224, 224W, 224C
HSC-221R/221RW/221RC
HSC-4R/-4RC
HSC-220R/220RW/220RC
NS6-221, 221W, 221C
*NS6-100, 100W, 100C
HSC-224R/224RW/224RC/RA/RST
*NS4-100, 100W, 100C
NS4-221, 221W, 221C
NS4-220, 220W, 220C
NS4-224, 224W, 224C
NS6-220, 220W, 220C
Resistor shown is for example
only. Not all annunciators
have in line resistance.
NS4 SERIES
UL LISTED
CONTROL
PANEL
PANEL
POWER
SUPPLY
NEGATIVE
UL LISTED
2-WIRE OPERATION
2-WIRE RELAY OPERATION
Annunciation device must be current limited to 20 mA @
24VDC Maximum. Not limiting current could result in
damage to the detector or cause a no alarm condition.
6
5
COM
N/C
4
3
N/O
N/O
HSC-(XXX)R (2-WIRE)
BLU
GRN
GRY
YEL
PUR
ORN
HSC-224RA/RST VERSION ONLY
TERMINAL BLOCK USED ON
LISTED
DEVICE
H1
ORN
YEL
H2
2
1
N/C
COM
END OF LINE
2 AND 4 WIRE BASE
RELAYS SHOWN WITH
HSC-4R
POWER OFF.
CONTACTS
HSC-RELAY SERIES
LISTED
RELAY
END OF LINE
HA-EOLR-12 OR HA-EOLR-24
HSC-4R
PUR
CONTROL
PANEL
INITIATING
CIRCUIT
HSC-4R
UL LISTED
POWER
SUPPLY
12VDC OR 24VDC
4-WIRE OPERATION
NOTE: The SLR-24/-24C/-24V/-24VC/-24VN/-24H/-24HC/-835/-835W/-835C/-835H/-835HW,
SLV-24/-24V/-24N/-24NW and SOC-24V/-24VN/-24VW have a built-in automatic sensitivity test feature.
LED
LED
LED
Test tool (back side)
Test tool
SOC-24V/-24VN
Magnet
LED marking
DIAGRAM B
For go/no-go testing, original test tool will be required.
1. Hold the test tool on the detector like Diagram B.
2. The detector should alarm within 10 seconds (If control panel is programmed for Fire Alarm
Verification, it may take up to 30 seconds).
3. The detector's LED should be on Red continuously and control panel indicating
appliances should activate.
4. Silence the system and activate the control panel reset to reset smoke detector.
5. The smoke detector LED should flash Green.
TESTING THE SOC-24V/-24VN/-24VW
NOTE:
In case of SOC-24V/-24VN/-24VW, only 1 LED
1
2
3 6
4
5
1
2
3 6
4
5
1
2
3 6
4
5
S1
S2 L2 L1
H1
H2
L4
L3
S1
S2 L2 L1
H1
H2
L4
L3
S1
S2 L2 L1
H1
H2
L4
L3
S1
S2 L2 L1
H1
H2
L4
L3