   the factory for servicing.  Refer to Technical Bulletin HA-97 for cleaning information.

4)  When the condition exists as stated in 2) the device needs to be cleaned or returned to

3)  In the alarm state both LEDs are on Red continuously.

2)  When the sensitivity drifts outside of its sensitivity limits,  both LEDs flash Red

SLR -24/-835/SLV-24 AND SOC-24V SERIES SENSITIVITY TEST FEATURE

1)  In normal condition both LEDs flash Green.

For go/no-go testing, a magnet will be required.

1.  Hold the magnet just UNDER the word "TEST" as shown on Diagram A.

2.  The detector should alarm within 10 seconds (If control panel is programmed for Fire Alarm
     Verification, it may take up to 30 seconds).
3.  The detector's LEDs should be on Red continuously and any control panel indicating appliances should activate.
4.  Silence the system and activate the control panel reset to reset smoke detector.
5.  The smoke detector LEDs should flash Green.

TESTING THE SLR-835/SLR-24  AND THE SLV-24 SERIES INSTALLATION

FIG. 1

DWG. # HA-06-060

PART# 1700-09987

(Pg.2 of 2, 06/16)

DIAGRAM A

FIG. 2

Hold Magnet
      Here

TEST

Testing is performed with the Hochiki America Alarm Test Magnet 

SIJ-24/-24C SENSITIVITY TEST PROCEDURE

POWER CONDITIONS MAY AFFECT SENSITIVITY.  ALWAYS RESET POWER PRIOR TO

within specified sensitivity limits and may require service.  See Tech Bulletin 

3). Place magnet on detector as shown in Figure 2 (opposite side).

source and with normal applied power, place magnet  as shown in Figure 1.

1). With detector wired to appropriate initiating circuit or current limited power

CONDUCT TESTING ONLY UNDER NORMAL STANDBY CONDITIONS.  ABNORMAL OR LOW

produce an alarm when magnet is positioned as in Figure 2, detector is not 

5). If detector does alarm when magnet is positioned as in Figure 1 or does not 

2). Wait at least six seconds.  Detector SHOULD not alarm and LED should  not light. 

TESTING OF NEXT UNIT.

4). Wait at least six seconds.  Detector SHOULD alarm.

HA-97 for more information and for additional sensitivity test devices.

NOTE:

SIJ-24/-24C DETECTOR

TOP VIEW OF

 (Part Number 0700-01110) shown below.

TEST DEVICE:

TEST PROCEDURE

TOP VIEW

SIDE VIEW

NS6-100

DEVICE

END OF LINE 

LISTED

EXCEPT NS6-100

(EXCEPT NS4-100)

N/A

47mA (75mA @ 18.0V MAX.)

HSC-4R12

LISTED

DEVICE

END OF LINE 

2

1 2-WIRE AUXILIARY RELAY BASE

4-WIRE 24V BASE

* - Requires External Current

Limiting To 150mA Max.

2

1

1

ID

HB-5

ALARM CURRENT

43mA (70mA @ 33.0V MAX.)

HB-4
HB-55

HB-4

HB-5
HB-3

HB-55
HB-73

HB-71
N/A

HB-72

1

49mA (62mA @ 30.0V MAX.)

46mA (77mA @ 33.0V MAX.)
150mA @ 15.0~33.0V MAX.

88mA (98mA @ 26.5V MAX.)

43mA (58mA @ 30.0V MAX.)

150mA @ 15.0~33.0V MAX.

46mA (77mA @ 33.0V MAX.)

93mA (136mA @ 33.0V MAX.)

43mA (70mA @ 33.0V MAX.)

43mA (58mA @ 30.0V MAX.)

93mA (136mA @ 33.0V MAX.)

HB-3

AND NS6 ARE IDENTICAL

- BASES WITH THE "W" SUFFIX 

ARE WHITE IN COLOR

NS6 SERIES

NOTE: - WIRING TERMINALS FOR THE NS4

BASE

NS6-224, 224W, 224C

HSC-221R/221RW/221RC

    HSC-4R/-4RC

HSC-220R/220RW/220RC

NS6-221, 221W, 221C

*NS6-100, 100W, 100C

HSC-224R/224RW/224RC/RA/RST

*NS4-100, 100W, 100C

NS4-221, 221W, 221C

NS4-220, 220W, 220C

NS4-224, 224W, 224C

NS6-220, 220W, 220C

Resistor shown is for example
only.  Not all annunciators
have in line resistance.

NS4 SERIES

UL LISTED

CONTROL

PANEL

PANEL

POWER
SUPPLY

NEGATIVE

UL LISTED

2-WIRE OPERATION

2-WIRE RELAY OPERATION

Annunciation device must be current limited to 20 mA @
24VDC Maximum. Not limiting current could result in
damage to the detector or cause a no alarm condition.

6

5

COM

N/C

4

3

N/O

N/O

HSC-(XXX)R (2-WIRE)

BLU
GRN

GRY

YEL

PUR

ORN

HSC-224RA/RST VERSION ONLY

TERMINAL BLOCK USED ON

LISTED

DEVICE

H1 

ORN

YEL

H2 

2

1

N/C

COM

END OF LINE 

2 AND 4 WIRE BASE
RELAYS SHOWN WITH

HSC-4R

POWER OFF.

CONTACTS

HSC-RELAY SERIES

LISTED 

RELAY

END OF LINE

HA-EOLR-12 OR HA-EOLR-24

HSC-4R

PUR

CONTROL

PANEL

INITIATING

CIRCUIT

HSC-4R

UL LISTED

POWER
SUPPLY

12VDC OR 24VDC

4-WIRE OPERATION

NOTE:  The SLR-24/-24C/-24V/-24VC/-24VN/-24H/-24HC/-835/-835W/-835C/-835H/-835HW,
SLV-24/-24V/-24N/-24NW and SOC-24V/-24VN/-24VW have a  built-in automatic sensitivity test feature.

LED

LED

LED

Test tool (back side)

Test tool

SOC-24V/-24VN

Magnet

LED marking

DIAGRAM B

For go/no-go testing, original test tool will be required.

1.  Hold the test tool on the detector like Diagram B.

2.  The detector should alarm within 10 seconds (If control panel is programmed for Fire Alarm
     Verification, it may take up to 30 seconds).
3.  The detector's LED should be on Red continuously and control panel indicating
      appliances should activate.
4.  Silence the system and activate the control panel reset to reset smoke detector.
5.  The smoke detector LED should flash Green.

TESTING THE SOC-24V/-24VN/-24VW

NOTE:

 In case of SOC-24V/-24VN/-24VW, only 1 LED

1

2

3 6

4

5

1

2

3 6

4

5

1

2

3 6

4

5

S1

S2 L2 L1

H1

H2

L4

L3

S1

S2 L2 L1

H1

H2

L4

L3

S1

S2 L2 L1

H1

H2

L4

L3

S1

S2 L2 L1

H1

H2

L4

L3

Отзывы: