Version 1.00 | March 2021 | MAN-1420HA
16 Channel IO Panel Module(S772) Information Guide
Страница 1: ...Version 1 00 March 2021 MAN 1420HA 16 Channel IO Panel Module S772 Information Guide ...
Страница 2: ...ice 6 Advanced Replacements 6 Overview 7 Use Case Examples 7 Package Contents 8 Installation 9 Before You Begin 10 Setting the Address 10 Placement 10 Wiring 13 Inputs 13 Outputs 14 Restrictions 15 Testing the Installation 16 Configuration 17 Hochiki America Corporation 16 Channel IO Panel Module S772 Information Guide Version 1 00 March 2021 MAN 1420HA Page 2 Contents ...
Страница 3: ... For channels set as Inputs 20 UL Compliance Limitations 21 Specifications 22 Electrical 22 Operating Environment 22 Physical Specifications 22 Index 23 Hochiki America Corporation 16 Channel IO Panel Module S772 Information Guide Version 1 00 March 2021 MAN 1420HA Page 3 Contents ...
Страница 4: ...difications not expressly approved by Hochiki America Corporation could void the user s authority to operate this equipment under the rules and regulations of the FCC Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interference received including interference that may cause undesired operation Installation Inst...
Страница 5: ... number is assigned when l Tech Support acknowledges a possible product failure l A product was damaged during shipping l An incorrect product was shipped l An order was placed using an incorrect part number l An order was placed using an incorrect part quantity l An order is no longer required Restocking fees may apply All returned products are tested to confirm operating failures experienced in ...
Страница 6: ...o all contractors who maintain an acceptable line of credit Initiate the advanced replacement process by requesting an RMA number from a Tech Support representative Advanced replacements can be shipped to your location when the product is covered under warranty and when a replacement product is in stock l Advanced replacements can be expedited at the request of the contractor Shipping costs associ...
Страница 7: ...bute or act upon cause and effect logic Use Case Examples The 16 Channel I O Interface can be used to interface the L titude panel to a NAC extender or Voice Evacuation system by providing l inputs to the L titude panel for dry contact closures such as General Trouble AC Power Trouble or Battery Trouble from these devices l outputs from the panel to control various NAC or Voice Evacuation outputs ...
Страница 8: ... panel to activate NAC outputs on these panels IMPORTANT Refer to the Wiring section for restrictions when using and wiring the 16 Channel I O Panel Module Package Contents l 1 Installation sheet l 1 Wiring Terminal Labels l 1 S772 16 Channel I O Interface Hochiki America Corporation 16 Channel IO Panel Module S772 Information Guide Version 1 00 March 2021 MAN 1420HA Page 8 Overview ...
Страница 9: ...ng field terminals q Connect field wiring as shown in the Wiring section below q Transfer the new configuration from Loop Explorer 2 into the panel q Wait for the Sending configuration to panel in LE2 and Saving configuration on the panel steps to complete q Remove AC and battery power from the panel q Remove the black plastic cover q Install the module into selected slot on the Main Back Board or...
Страница 10: ...ed for handling circuit boards Setting the Address Panel modules should use addresses 1 8 Each panel module of the FireNET L titude Fire Alarm Control Panel must contain a unique setting before being connected to the Main Back Board The binary setting of the DIP switch sets the specific address for the panel module The numeric order of the address setting between modules does not impact operation ...
Страница 11: ... protective packaging using adequate electrostatic protection 4 Point the conductor side of the panel module toward the backplate 5 Insert the notched end of the panel module in the metal guide notch of the backplate at an angle as shown Hochiki America Corporation 16 Channel IO Panel Module S772 Information Guide Version 1 00 March 2021 MAN 1420HA Page 11 Installation ...
Страница 12: ...klist above for details on placement 6 Rotate the panel module until all conductors are securely inserted into connectors of the Main Back Board 7 Replace the cover onto the Main Back Board 8 Reconnect the batteries and restore AC power Hochiki America Corporation 16 Channel IO Panel Module S772 Information Guide Version 1 00 March 2021 MAN 1420HA Page 12 Installation ...
Страница 13: ...hin a UL listed system Inputs on the 16 Channel I O Interface are intended to be activated by connecting the input to a 0V terminal through volt free contacts Contacts must be suitably rated to handle 24VDC The switch current caused by contact closure is limited to a maximum of 3mA Hochiki America Corporation 16 Channel IO Panel Module S772 Information Guide Version 1 00 March 2021 MAN 1420HA Page...
Страница 14: ...f the suppression diode to the positive terminal of the relay coil as shown to provide protection Each output is rated up to 100mA therefore a 100mA fuse must be used to provide protection Multiple channels may be protected with a single 100mA fuse if their combined currents will not exceed 100mA This example shows 2 LEDs protected by a single fuse The combined current draw of these LEDs will not ...
Страница 15: ...field wiring and wiring terminal locations Restrictions Inputs are intended for use as control signals from other life safety equipment Inputs of this device are not supervised and therefore cannot be used directly as initiating circuits for life safety applications within a UL listed system Outputs are intended for use as control signals to other life safety equipment Outputs of this device are n...
Страница 16: ...ing LED 2 Rx Comms Green Flashes every 2 3 seconds when the module is receiving data from the panel LED 3 Tx Comms Green Flashes every 2 3 seconds when the module is transmitting data to the panel LED 4 Trouble Yellow Flashes every 2 seconds when one or more outputs have a trouble condition LED 5 Input Active LED Red Flashes every 2 seconds when one or more inputs are active LED 6 Output Active LE...
Страница 17: ...nfiguration via Loop Explorer 2 or an Autolearn on the panel Panel Module Properties Set each of the 16 channels to be either an input or an output for each 16 Channel I O Panel Module installed in the FireNET L titude Fire Alarm Control Panel Hochiki America Corporation 16 Channel IO Panel Module S772 Information Guide Version 1 00 March 2021 MAN 1420HA Page 17 Configuration ...
Страница 18: ...ked the Second Delay field is displayed 3 Each output circuit is normally floating but is pulled low to 0V when activated Selecting Output Invert will set the circuit to normally be pulled low to 0V but become floating when activated 4 Ignore Global Delays This setting controls the delay of the activation of the output If unchecked it will activate based on the Global Delay settings in the Panel S...
Страница 19: ...e output will be delayed based on the settings in the Second Delay field 5 Enter a Duration to select how long an output will be active If set to 0 it will remain active until the system is reset For UL compliance this field must be set to 0 6 Set the Location Text up to 80 characters 7 Use the Map to Zone field to set the zone number for the circuit Allowable values are 0 2000 Hochiki America Cor...
Страница 20: ...if those outputs have configured delays For UL compliance this field must be checked 4 Set the Input Delay in seconds up to 180 seconds Input activation will prevent the panel s response for specified time period when the input is activated No activation will occur if the input state is reset to normal before time period expires For UL compliance this field must be set to 0 Hochiki America Corpora...
Страница 21: ...s In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems UL 864 10th Edition certain programming features or options must be limited to specific values or not used at all as indicated below Field Configurable Range UL Permitted Value Range First Delay 0 10 minutes 0 minutes Second Delay 0 10 minutes 0 minutes Duration 0 sec...
Страница 22: ...pe open collector l Voltage range 0 24 VDC l Maximum current per channel 100mA l Maximum sum total current for channels 1 8 400 mA l Maximum sum total current for channels 9 16 400 mA Over current conditions may result in component failure Operating Environment Dry indoor use only Temperature Range 5oC 49oC or 23oF 120oF Relative Humidity Up to 95 non condensing Physical Specifications Dimensions ...
Страница 23: ...ral Trouble 7 H Heartbeat 16 L Loop Explorer 2 9 17 M Main Back Board 9 N NAC 7 S Standby Batteries 11 T Terminals 9 Trouble 7 Hochiki America Corporation 16 Channel IO Panel Module S772 Information Guide Version 1 00 March 2021 MAN 1420HA Page 23 Index ...