Terminal Identification: 

Terminal Legend  Function/Description 

L, N 

Connect 220VAC 50/60Hz to these terminals: L to hot, N to neutral. Do not use the [G] terminal. 

+ DC --- 

8 amp supply current in non-alarm condition with 10 amp supply current during alarm for Fire 
Alarm Applications. 10 amp supply current for Access Control Applications. 

 

AC Fail 
NC, C, NO 

Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally 
energized when AC power is present. Contact rating 1 amp @ 28VDC. AC or brownout fail is 
reported within 1 minute of event. To delay reporting for up to 6 hrs., cut “AC delay” jumper 
and reset power to unit. 

 

Bat Fail 
NC, C, NO 

Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC 
power is present. Contact rating 1 amp @ 28VDC. A removed battery is reported within 5 minutes. 
Battery reconnection is reported within 1 minute. 

Low battery threshold: 24VDC output threshold set @ approximately 21VDC. 

– BAT + 

Stand-by battery connections. Maximum charge current 3.6 amp. 

Stand-by Specifications 

(total current shown)

Output 

15 min. of Stand-by & 

5 min. of Alarm 

4 hr. of Stand-by & 

5 min. of Alarm 

24 hr. of Stand-by & 

5 min. of Alarm 

60 hr. of Stand-by & 

5 min. of Alarm 

24VDC / 12AH 

Battery 

Stand-By = 8 amp 

Alarm = 10 amp 

Stand-By = 1.5 amp 

Alarm = 10 amp 

Stand-By = 200mA 

Alarm = 10 amp 

Stand-By = 100mA 

Alarm = 10 amp 

Output 

15 min. of Stand-by & 

5 min. of Alarm 

4 hr. of Stand-by & 

5 min. of Alarm 

24 hr. of Stand-by & 

15 min. of Alarm 

60 hr. of Stand-by & 

15 min. of Alarm 

24VDC / 65AH 

Battery 

 

----------------------------------------------- 

Stand-By = 8.0 amp 

Alarm = 10 amp 

Stand-By = 1.5 amp 

Alarm = 10 amp 

Stand-By = 500mA 

Alarm = 10 amp 

For Access Control applications battery capacity for 10 amp supply current - 1 hr. for 24VDC/12AH battery, 
6.5 hrs. for 24VDC/65AH battery. 
See battery size calculation worksheet for other batteries (

Page 5

). 

 

Wiring: 

USE 14 AWG or larger for all power connections. 

Note: 

Take care to keep power-limited circuits separate from non-power limited wiring (220VAC, Battery). 

 

Maintenance: 

Unit should be tested at least once a year for the proper operation as follows: 

Output Voltage Test: 

Under normal load conditions the DC output voltage should be checked for proper voltage level. 

Battery Test: 

Under normal load conditions check that the battery is fully charged, check specified voltage both at the bat- 

tery terminal and at the board terminals marked [- BAT +] to ensure that there is no break in the battery connection wires. 

Note: 

Maximum charging current under discharges is 3.6 amp. 

Note: 

Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed. 