Hochiki FN-1024X-220 Скачать руководство пользователя страница 3

- 3 - 

 

LED Diagnostics: 

Red (DC)  Green (AC)  Power Supply Status 

ON 

ON 

Normal operating condition. 

ON 

OFF 

Loss of AC. Stand-by battery supplying power. 

OFF 

ON 

No DC output. 

OFF 

OFF 

Loss of AC. Discharged or no stand-by battery. No DC output. 

 

Fig. 1 

CAUTION: De-energize unit prior to servicing. For continued protection 
against risk of electric shock and fire hazard replace fuses with the same type 
and rating. Do not expose to rain or moisture. 

 
 
 
 
 
 

 

DC Output to devices 

 
 
 

 

 

 

220VAC 

power mains 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 

 

BAT F 

Battery 

Connections 

 

 

Class 1 

 

Earth Ground 

 
 

Wire Strap 

(from 

Enclosure 

to Door) 

Do Not Touch 

Exposed Metal Parts 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Optional Rechargeable 

Stand-by Battery 

 

Optional Rechargeable 

Stand-by Battery 

 
 

 

CAUTION: Optional rechargeable stand-by batteries must match 

the power supply output voltage setting. 

Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing. 

15

 

   

 

 

 

AC DELAY 

L G 

AIL NC C NO NC C NO AC FAIL 

AC DC 

Battery and AC 

Supervision Circuit 

5

A

 2

5

0

V

 

1

5

A

 3

2

V

 

 B

A

T

 +

 

+

 D

C

 -

--

 