TYPICAL MOUNTING ARRANGEMENT

STANDARD 4" SQ
ELECTRICAL BOX

CAUTION !

GENERAL DESCRIPTION

CAUTION !

INSTALLATION INSTRUCTIONS FOR DCP-CZM CONVENTIONAL ZONE MODULE

MOUNTING REQUIREMENTS

The (DCP-CZM) Conventional Zone module is mounted as 

WIRING

NOTE: All  wiring must  conform to local codes,  

ordinances and regulations.

1)  Install module  wiring in  accordance  with  the job

drawings and appropriate wiring diagram (see Fig.3).

2)  Secure the  module  to a U.L. listed  electrical box

(supplied by installer), as shown in Figure 2.

shown in Figure 2 on page 1 of this instruction.

HOCHIKI AMERICA CORPORATION

7051 VILLAGE DRIVE, SUITE 100

BUENA PARK, CA 90621-2268

PROGRAMMING PLUG AND CONNECTOR 

EXPLODED VIEW OF ADDRESS

FIGURE 1.

NON-POLARIZED

PLUG IS

TO PROGRAMMER

NOTE: Please reference the 2 wire detector compatibility matrix on 

 the proceding page for a complete list of devices approved for use 

with the "DCP-CZM"

The information contained in this installation instruction is to be used as quick reference guide. For detailed system 

information, refer to the panel's installation manual. 

CAUTION !

Install the modules in this instruction in

accordance with applicable NFPA

standards, local codes, and the authorities

having jurisdiction.  Failure to follow these

instructions may result in failure of the

system to operate as intended.

Hochiki America is not responsible for

modules that have been improperly

installed, tested, or maintained.

To ensure proper operation

connect this module to a

compatible Fire Control Panel

only.  Refer to panel instructions

for proper connection and

compatibility.

If this module will be installed in an

existing operation system, inform the

operator and local authority that the

system will be temporarily out of

service.  Disconnect power to the

control panel before installing the

module

An average of 6.75mA (communication current) 

per loop of SLC devices, must be factored into 

the panel battery backup calculations.

PART# 1700-10170

(PG 1 OF 2,  05/17)

HA-06-101

DWG. #

μ

This instruction applies to the Conventional Zone Module (DCP-CZM), which is

to be connected to a Signal Line Circuit (SLC). The module  allows the analog panel
to interface and monitor dry contacts such as pull stations and two-wire
conventional smoke detectors. The "DCP-CZM" is addressed through the
communication line of the system and transmits the status of one zone of devices
to the panel. Status conditions are reported as normal, open or alarm. It supervises
the external power supply as well as the entire zone of devices.

NOTE: 

NOTE: Maximum Ripple Voltage 2VDC P-P