background image

- 2 - 

 

Overview: 

The FN-600X-220 is a power supply that converts a 220VAC 50/60Hz input to a 12VDC or 24VDC regulating output 
(see specifications below). 

 

Input: 

 

Input 220VAC 50/60Hz, 1.5 amp. 

Output: 

 

12VDC or 24VDC selectable output. 

Specifications:

 

Supervision: 

 

AC fail supervision (form “C” contacts). 

 

Low battery supervision (form “C” contacts). 

 

Battery presence supervision (form “C” contacts). 

 

 

6 amp continuous supply current at 12VDC or  24VDC. 

 

Filtered and electronically regulated outputs. 

 

Short circuit and thermal overload protection. 

Battery Backup: 

 

Built-in charger for sealed lead acid or gel type  batteries. 

 

Automatic switch over to stand-by battery when AC fails. 

 

Maximum charge current 0.7 amp. 

 

Zero voltage drop when switched over to 
battery backup. 

Additional Features: 

 

AC input, DC output and BAT trouble LED  indicators. 

 

Power supply, enclosure, cam lock and battery  leads. 

Enclosures: 

FN-600X-R220 (Red Enclosure) 
FN-600X-C220 (Charcoal Grey Enclosure) 

Enclosure Dimensions 

(H x W x D)

13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm) 

 

Installation Instructions: 

The unit should be installed in accordance with article 760 of The National Electrical Code as well as NFPA 72 and all 
applicable Local Codes. 
1.

 

Mount unit in the desired location

Mark and predrill holes in the wall to line up with the top two keyholes in the 

enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s 
upper keyholes over the two upper screws; level and secure. Mark the position of the lower two holes. Remove the 
enclosure. Drill the lower holes and install two fasteners. Place the enclosure’s upper keyholes over the two upper 
screws. Install the two lower screws and make sure to tighten all screws 

(Enclosure Dimensions, pg. 4)

2.

 

The power supply is pre-wired to the ground (chassis). Connect main incoming ground to the provided green 
grounding conductor lead. Connect unswitched AC power (220VAC, 50/60 Hz to terminals marked [L, G, N] 

(Fig. 1, pg. 4)

. Use 14 AWG or larger for all power connections (Battery, DC output, AC input). Use 22 AWG to 

18 AWG for power-limited circuits (AC Fail/Low Battery  reporting). 

Keep power-limited wiring separate from non power-limited wiring (220VAC, 50/60Hz Input, DC Output, 
Battery Wires). Minimum 0.25” spacing must be provided. 
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. 
There are no user serviceable parts inside. Refer installation and servicing to qualified service  personnel. 

3.

 

Set the unit to the desired DC output voltage by setting SW1 

(Fig. 1, pg. 4) 

to the appropriate position 

(Power Supply Voltage Output Selections Chart, pg. 2). 

4.

 

Measure output voltage before connecting any devices to ensure proper operation. Improper or high voltage will 
damage these devices. When servicing the unit, AC mains should be removed. 

5.

 

Connect devices to be powered to terminals marked [+ DC -], carefully observing correct polarity (

Fig. 1, pg. 4

). 

6.

 

For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in the 
loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type. 

7.

 

Connect appropriate signaling notification devices to terminals marked [AC FAIL & BAT FAIL] 

(Fig. 1, pg. 4), 

supervisory relay outputs. 

Note: 

When used in fire alarm, burglar alarm or access control applications, “AC Fail” relay should be utilized 

to visually indicate that AC power is on. To delay report for 6 hours, cut “AC Delay” jumper 

(Fig. 1, pg. 4)

8.

 

Please ensure that the cover is secured with the provided Key Lock. 

Power Supply Output Specifications: 

 

Output  Switch Position 

12VDC  SW1 - CLOSED 

(Fig. 1a, pg. 4) 

24VDC  SW1 - OPEN 

(Fig. 1a, pg. 4) 

Отзывы: