background image

 

HOBO MX Temp/RH Data Logger (MX1101) Manual 

 

1-508-759-9500 (U.S. and International) 6 

www.onsetcomp.com 

1-800-LOGGERS (U.S. only) 

when the logger’s LCD screen refreshes every 15 
seconds. 

 

The actual values for the high and low alarm limits are set 
to the closest value supported by the logger. In addition, 
alarms can trip or clear when the sensor reading is within 
the resolution specifications. This means the value that 
triggers the alarm may differ slightly from the value 
entered. 

 

When you download data from the logger, alarm events 
can be displayed on the plot or in the data file. See 

Logger Events

 

Once cleared, an audible alarm starts beeping again if the 
sensor values go out of the normal range. Even if an 
audible alarm is cleared, a visual alarm may remain on 
the logger LCD and in the app depending on the settings 
selected for maintaining visual alarms or because the 
alarm condition may still be in effect. In addition, an 
audible alarm continues beeping when the sensor values 
have returned to the normal range until it is cleared as 
described in step 10. 

 

Although an audible alarm and a visual alarm can occur 
at the same time when a sensor alarm is tripped, they are 
cleared in different ways. The audible alarm can be 
cleared as described in step 10. Meanwhile, a visual 
alarm is cleared as determined by the setting selected for 
Maintain Visual Alarm Until configuration setting. This 
means you could clear a beeping audible alarm and the 
visual alarm remains on the LCD and in the app until the 
logger is reconfigured, the sensor is in limits, or the alarm 
button is pressed—depending on the setting you 
selected. 

 

If the logger is configured to stop logging with a button 
push, any tripped alarms are cleared automatically when 
logging is stopped and no Alarm Cleared event is logged. 
This ensures that the logger starts checking for alarm 
conditions when logging resumes (if the logger was 
configured with Allow Button Resume selected). 

Burst Logging 

Burst logging is a logging mode that allows you to set up more 
frequent logging when a specified condition is met. For 
example, a logger is recording data at a 5-minute logging 
interval and burst logging is configured to log every 30 seconds 
when the temperature rises above 85°F (the high limit) or falls 
below 32°F (the low limit). This means the logger records data 
every 5 minutes as long as the temperature remains between 
85°F and 32°F. Once the temperature rises above 85°F, the 
logger switches to the faster logging rate and records data 
every 30 seconds until the temperature falls back to 85°F. At 
that time, logging then resumes every 5 minutes at the fixed 
logging interval. Similarly, if the temperature falls below 32°F, 
then the logger switches to burst logging mode again and 
record data every 30 seconds. Once the temperature rises back 
to 32°F, the logger then returns to fixed mode, logging every 5 
minutes. 

Note:

 Sensor alarms, statistics, and the Stop Logging 

option Never Stop (Overwrites Old Data) are not available in 
burst logging mode. 

To set up burst logging: 

1.

 

Tap Devices. Press the Start/Stop button on the logger to 
wake it up, if necessary. 

2.

 

Tap the logger tile in the app to connect to the logger and 
tap Configure & Start. 

3.

 

Tap Logging Mode and then tap Burst Logging. 

4.

 

Set the burst logging interval, which must be faster than the 
logging interval. Keep in mind that the faster the burst 
logging rate, the greater the impact on battery life and the 
shorter the logging duration. Because measurements are 
being taken at the burst logging interval throughout the 
deployment, the battery usage is similar to what it would be 
if you had selected this rate for the normal logging interval. 

5.

 

Select Low and/or High and type a value to set the low 
and/or high values. 

6.

 

Repeat step 5 for the other sensor if desired. 

Notes: 

 

The high and low burst limits are checked only when the 
logger's LCD screen refreshes once every 15 seconds. If 
you set the logging interval to less than 15 seconds and 
the sensor reading falls outside the levels, burst logging 
does not begin until the next 15-second refresh cycle. 

 

If high and/or low limits are configured for more than 
one sensor, burst logging begins when any high or low 
condition goes out of range. Burst logging does not end 
until all conditions on all sensors are back within normal 
ranges. 

 

The actual values for the burst logging limits are set to 
the closest value supported by the logger. 

 

Burst logging mode can begin or end when the sensor 
reading is within the resolution specifications. This means 
the value that triggers burst logging may differ slightly 
from the value entered.  

 

Once the high or low condition clears, the logging 
interval time is calculated using the last recorded data 
point in burst logging mode, not the last data point 
recorded in fixed mode. For example, a logger has a 10-
minute logging interval and logs a data point at 9:05. 
Then, the high limit is surpassed and burst logging begins 
at 9:06. Burst logging then continues until 9:12 when the 
sensor reading falls back below the high limit. Now back 
in fixed mode, the next logging interval is 10 minutes 
from the last burst logging point, or 9:22 in this case. If 
burst logging had not occurred, the next data point 
would have been at 9:15. 

 

A New Interval event is created each time the logger 
enters or exits burst logging mode. See 

Logger Events

 for 

details on plotting and viewing the event. In addition, if 
the logger is stopped with a button push while in burst 
logging mode, a New Interval event is automatically 
logged and the burst condition is cleared, even if the 
actual high or low condition has not cleared. The logger 
checks the high and low conditions when logging 
resumes (if the logger is configured with Allow Button 
Resume selected). 

Statistics Logging 

During fixed logging, the logger records data for enabled 
sensors and/or selected statistics at the logging interval 

Содержание MX1101

Страница 1: ...s 2 2 mph RH 20 seconds to 90 in airflow of 1 m s 2 2 mph Logger Radio Power 1 mW 0 dBm Transmission Range Approximately 30 5 m 100 ft line of sight Wireless Data Standard Bluetooth Low Energy Blueto...

Страница 2: ...taneously for 3 seconds to reset a logger password Alarm Stats Button Press this button for 1 second to switch between statistics alarm readings and the current sensor readings as applicable or to sil...

Страница 3: ...ing the logger deployment Press the Alarm Stats button to view this reading Press the Alarm Stats button again to cycle through any statistics defined above and ultimately back to the current sensor r...

Страница 4: ...u can then filter the list of devices to show only loggers marked as favorites Make the logger beep one time to help you locate it HELLO also appears on the LCD when the logger is paged Update the fir...

Страница 5: ...d Press the start button on the logger if you set it up to start logging with a button push Deploy the logger using the mounting materials see Mounting the Logger After logging begins you can read out...

Страница 6: ...ns to fixed mode logging every 5 minutes Note Sensor alarms statistics and the Stop Logging option Never Stop Overwrites Old Data are not available in burst logging mode To set up burst logging 1 Tap...

Страница 7: ...or a minute and use the 12 samples to record the resulting statistics at each 1 minute logging interval Note that the faster the sampling rate the greater the impact on battery life Because measuremen...

Страница 8: ...ation Remove the battery immediately and dry the circuit board Note Static electricity may cause the logger to stop logging The logger has been tested to 8 KV but avoid electrostatic discharge by grou...

Страница 9: ...his device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation FCC Caution Any changes or modifications...

Отзывы: