5-2. Weld Output Terminals And Selecting Cable Sizes
NOTICE
−
The Total Cable Length in Weld Circuit (see table below) is the combined length of both weld cables. For example, if the power source is
100 ft (30 m) from the workpiece, the total cable length in the weld circuit is 200 ft (2 cables x 100 ft). Use the 200 ft (60 m) column to determine cable
size.
Weld Cable Size** and Total Cable (Copper) Length in Weld Circuit
Not Exceeding***
100 ft (30 m) or Less
150 ft
(45 m)
200 ft
(60 m)
250 ft
(70 m)
300 ft
(90 m)
350 ft
(105 m)
400 ft
(120 m)
Welding
Amperes
10
−
60%
Duty Cycle
AWG (mm
2
)
60
−
100%
Duty Cycle
AWG (mm
2
)
10
−
100% Duty Cycle
AWG (mm
2
)
100
4 (20)
4 (20)
4 (20)
3 (30)
2 (35)
1 (50)
1/0 (60)
1/0 (60)
150
3 (30)
3 (30)
2 (35)
1 (50)
1/0 (60)
2/0 (70)
3/0 (95)
3/0 (95)
200
3 (30)
2 (35)
1 (50)
1/0 (60)
2/0 (70)
3/0 (95)
4/0 (120)
4/0 (120)
250
2 (35)
1 (50)
1/0 (60)
2/0 (70)
3/0 (95)
4/0 (120)
2 ea. 2/0
(2x70)
2 ea. 2/0
(2x70)
300
1 (50)
1/0 (60)
2/0 (70)
3/0 (95)
4/0 (120)
2 ea. 2/0
(2x70)
2 ea. 3/0
(2x95)
2 ea. 3/0
(2x95)
350
1/0 (60)
2/0 (70)
3/0 (95)
4/0 (120)
2 ea. 2/0
(2x70)
2 ea. 3/0
(2x95)
2 ea. 3/0
(2x95)
2 ea. 4/0
(2x120)
*
This chart is a general guideline and may not suit all applications. If cable overheats, use next size larger cable.
**Weld cable size (AWG) is based on either a 4 volts or less drop or a current density of at least 300 circular mils per ampere.
( ) = mm
2
for metric use
***For distances longer than those shown in this guide, see AWS Fact Sheet No. 39, Welding Cables, available from the American Welding
Society at http://www.aws.org.
Ref. S-0007-M 2017
−
08
5-3. Connecting Weld Output Cables
803778-B
!
Turn off power before connecting to
weld output terminals.
!
Failure to properly connect weld
cables may cause excessive heat
and start a fire, or damage your ma-
chine.
.
Do not place anything between weld
cable terminal and copper bar. Make
sure that the surfaces of the weld cable
terminal and copper bar are clean.
1
Correct Weld Cable Connection
2
Incorrect Weld Cable Connection
3
Weld Output Terminal
4
Supplied Weld Output Terminal Nut
5
Weld Cable Terminal
6
Copper Bar
Remove supplied nut from weld output ter-
minal. Slide weld cable terminal onto weld
output terminal and secure with nut so that
weld cable terminal is tight against copper
bar.
Tools Needed:
3/4 in. (19 mm)
4
2
3
1
5
6
connecting weld output cables 3
−
2010
Содержание IronMan 240
Страница 4: ......
Страница 26: ... A complete Parts List is available at www HobartWelders com OM 284833 Page 22 5 13 Weld Parameters ...
Страница 27: ... A complete Parts List is available at www HobartWelders com OM 284833 Page 23 284702 B ...
Страница 32: ...OM 284833 Page 28 SECTION 8 ELECTRICAL DIAGRAM Figure 8 1 Welding Power Source Circuit Diagram ...
Страница 33: ...OM 284833 Page 29 284828 A ...