b. Line-drop current transformers
The three line-drop current transformers
(9),
in conjunction with burden resistors
(8),
detect
the magnitude and power factor of current flowing from generator to load. They feed a signal
to the voltage regulator which interprets the signal and alters the exciter field current as
required to maintain a constant predetermined voltage at the load
(see Voltage Regulator
Manual No. TM-232).
c. Overload current transformers
Three overload current transformers
(3),
in conjunction with burden resistors
(1),
monitor the
output load current in each of the three output phases, and supply a reduced value current
signal to the overload module
(7).
(3)
Overload module
The overload module
(7)
is a solid-state device designed to interpret a signal from transformers
(3)
and to send a signal to the protective monitor module
(4, Fig. 8)
when an overload condition
exists in any generator output phase. A pull-apart electrical connector is mounted on the
overload module to provide quick-disconnect facilities for all wiring to the module. The overload
module is equipped with a hermeticallysealed, reed-type relay. Relay contacts are normally
open. The solidstate circuitry is designed to close relay contacts when output current in ANY
phase reaches 125% of normal rated output capacity. The closed relay sends a signal to the
protective monitor. This signal “gates” the overload SCR
(silicone-controlled rectifier)
in the
protective monitor and interrupts the load contactor holding circuit, allowing the load contactor to
open.
The following is a list of overload module characteristics:
NOTE: The overload protective system will function when any phase carries 123% to 127% of rated
load.
•
At 125% load the module will function in 4 minutes.
•
At 150% load the module will function in 16 seconds.
•
At 200% load the module will function in 4 seconds.
NOTE:
All times are plus or minus 25% and are nonadjustable.
(4)
Rectifier
A diode-bridge rectifier
(5)
receives 400-Hz AC from phase C of the generator output an
converts it to a pulsating, direct current for energization of the load contactor holding coil only.
This DC coil-holding circuit is controlled indirectly be controlling the 400-Hz AC to the rectifier.
The ground circuit for the rectifier’s AC supply must pass through the relay contacts in the
protective monitor module to ground cable N. Therefore, any time a protective device functions
to open the protective monitor relay, the rectifier’s AC circuit is opened. No DC is then available
for the load contactor holding coil, hence, the load contactor opens.
(5)
Terminal boards
Three terminal boards
(2)
provide connection facilities for small leads.
OM-499
May 31/94 Revised
1-1
Page 21
Содержание 6824-1
Страница 2: ...This page intentionally left blank...
Страница 6: ...This page intentionally left blank OM 499 Safety Warnings May 31 94 Revised Page 4...
Страница 8: ...This page intentionally left blank OM 499 Introduction May 31 94 Revised Page 2...
Страница 14: ...This page intentionally left blank OM 499 Table of Contents May 31 94 Revised Page 6...
Страница 39: ...No 2 Output Control Figure 14 No 2 Power Module Panel Figure 15 OM 499 May 31 94 Revised 1 1 Page 25...
Страница 40: ...This page intentionally left blank OM 499 1 1 May 31 94 Revised Page 26...
Страница 66: ...Engine Control Panel in Tilt out Position Figure 8 OM 499 2 1 May 31 94 Revised Page 12...
Страница 90: ...No 2 Output on Dual Output Units Figure 13 OM 499 2 3 May 31 94 Revised Page 20...
Страница 97: ...Test Receptacle Connector Terminals Identification Figure 4 OM 499 May 31 94 Revised 3 1 Page 7...
Страница 98: ...This page intentionally left blank OM 499 3 1 May 31 94 Revised Page 8...
Страница 114: ...This page intentionally left blank OM 499 3 1 May 31 94 Revised Page 24...
Страница 122: ...Generator Set Figure 1 OM 499 4 3 May 31 94 Revised Page 2...
Страница 124: ...Canopy Assembly Figure 2 OM 499 4 3 May 31 94 Revised Page 4...
Страница 126: ...This page intentionally left blank OM 499 4 3 May 31 94 Revised Page 6...
Страница 128: ...Canopy Assembly Figure 3 OM 499 4 3 May 31 94 Revised Page 8...
Страница 130: ...This page intentionally left blank OM 499 4 3 May 31 94 Revised Page 10...
Страница 132: ...Generator Set Without Canopy Figure 4 OM 499 4 3 May 31 94 Revised Page 12...
Страница 134: ...This page intentionally left blank OM 499 4 3 May 31 94 Revised Page 14...
Страница 136: ...Radiator and Cooling System Group Figure 5 OM 499 4 3 May 31 94 Revised Page 16...
Страница 138: ...Air Cleaner Assembly Figure 6 OM 499 4 3 May 31 94 Revised Page 18...
Страница 140: ...Electric Governor Assembly Woodward Governor Kit Part No 488701 Figure 7 OM 499 4 3 May 31 94 Revised Page 20...
Страница 142: ...Fuel Lines Assembly Figure 8 OM 499 4 3 May 31 94 Revised Page 22...
Страница 144: ...Oil Line Assembly Figure 9 OM 499 4 3 May 31 94 Revised Page 24...
Страница 146: ...Fuel Oil Lines Figure 10 OM 499 4 3 May 31 94 Revised Page 26...
Страница 148: ...Fuel Oil Lines Figure 11 OM 499 4 3 May 31 94 Revised Page 28...
Страница 150: ...Stator Terminal Panel Assembly Figure 12 OM 499 4 3 May 31 94 Revised Page 30...
Страница 152: ...Power Module Panel Assembly Figure 13 OM 499 4 3 May 31 94 Revised Page 32...
Страница 154: ...This page intentionally left blank OM 499 4 3 May 31 94 Revised Page 34...
Страница 156: ...Control Box Assembly Figure 14 OM 499 4 3 May 31 94 Revised Page 36...
Страница 158: ...Generator Controls Tray Assembly Figure 15 OM 499 4 3 May 31 94 Revised Page 38...
Страница 160: ...This page intentionally left blank OM 499 4 3 May 31 94 Revised Page 40...
Страница 162: ...Protective Relays Tray Assembly Figure 16 OM 499 4 3 May 31 94 Revised Page 42...
Страница 164: ...This page intentionally left blank OM 499 4 3 May 31 94 Revised Page 44...
Страница 166: ...Control Box and Internal Components Group Figure 17 OM 499 4 3 May 31 94 Revised Page 46...
Страница 168: ...Engine Control Panel Assembly Figure 18 OM 499 4 3 May 31 94 Revised Page 48...
Страница 170: ...This page intentionally left blank OM 499 4 3 May 31 94 Revised Page 50...
Страница 172: ...Output Terminal Board Assembly Figure 19 OM 499 4 3 May 31 94 Revised Page 52...
Страница 174: ...Generator Group Figure 20 OM 499 4 3 May 31 94 Revised Page 54...
Страница 176: ...Mounting Frame and Lifting Yoke Assembly Figure 21 OM 499 4 3 May 31 94 Revised Page 56...
Страница 178: ...Auxiliary Frame and Components Group Figure 22 OM 499 4 3 May 31 94 Revised Page 58...
Страница 180: ...Electric Governor Assembly OM 499 4 3 May 31 94 Revised Page 60...
Страница 182: ...This page intentionally left blank 4 3 March 31 74 Revised Page 21A OM 499...
Страница 194: ...This page intentionally left blank OM 499 4 4 May 31 94 Revised Page 12...
Страница 196: ...This page intentionally left blank OM 499 5 0 May 31 94 Revised Page 2...
Страница 198: ...This page intentionally left blank OM 499 6 0 May 31 94 Revised Page 2...
Страница 199: ......
Страница 200: ......
Страница 201: ......
Страница 202: ......
Страница 203: ......
Страница 204: ......
Страница 205: ......
Страница 206: ......
Страница 207: ......
Страница 208: ......
Страница 209: ......
Страница 210: ......
Страница 212: ...This page intentionally left blank OM 499 Unusual Service Conditions May 31 94 Revised Page 2...
Страница 214: ......