 INMBSMID---I000

 

     

User’s Manual r

1.3 EN

 

 

  

 

 

 

 

 

 

© HMS Industrial Networks S.L.U - All rights reserved 

This information is subject to change without notice

 

 

  URL    https://www.intesis.com  

 
 

                9 / 24

 

4

 

Modbus Interface Specification 

4.1

 

Modbus physical layer 

 

INMBSMID---I000 implements a Modbus RTU (Slave) interface, to be connected to an EIA-
485  line.  It  performs  an  8N2  communication  (8  data  bits,  no  parity  and  2  stop  bit)  with 
several  available  baud  rates  (2400  bps,  4800  bps,  9600  bps  -default-,  19200  bps,  38400 
bps, 57600 bps, 76800 bps and 115200 bps). It also supports 8N1 communication (8 data 
bits, no parity and 1 stop bit).

  

 

4.2

 

Modbus Registers for INMBSMID001I000 

 

All  registers  are 

type  “16

-

bit  unsigned  Holding  Register”

  and  use  the  standard 

ModBus  big 

endian 

notation. 

 
The indoor unit (IU) that is being controlled must have Unit Address 

0

. This address needs to 

be set in the AC unit.  

4.2.1  Control and status registers  

 

Register Address 

(protocol address) 

Register Address  

(PLC address) 

R/W  Description 

R/W 

AC unit On/Off 

 

0: Off 

 

1: On

 

R/W 

AC unit Mode 

1

 

 

0: Auto (Default value) 

 

1: Heat 

 

2: Dry 

 

3: Fan 

 

4: Cool

 

R/W 

AC unit Fan Speed 

1

 

 

0: Auto (Default value) 

 

1: SP1 

 

2: SP2 

 

3: SP3 

R/W 

AC unit Up/Down Vane Position 

1

 

 

0:   Off (Default value) 

 

10: Swing 

 

R/W 

AC unit Temperature setpoint 

1,2,3 

 

-32678 (Initialization value) 

 

17..30 ºC (ºC/x10ºC) 

 

63..86 ºF  

AC unit Temperature reference 

1,2,3

  

 

-32678 (Initialization value) 

 

Ranges determined by the Manufacturer 

of the AC indoor unit. (ºC/x10ºC/ºF)

 

R/W 

Window Contact 

 

0: Closed (Default Value) 

 

1: Open

 

 

                                           

1

  Available  values  will  depend  on  the  AC  unit  mode.  Check  the  AC  unit  model  functions  in  its  User  Manual  to  know  the  possible 

values for this register. 

2

  Magnitude  for  this  register  can  be  adjusted  to  Celsius  x  1ºC,  Celsius  x  10ºC  (default)  or  Fahrenheit.  See  section  4.5  for  more 

information. 

3

 It is not possible turn the value shown in Fahrenheit to x10. 

Содержание Intesis INMBSMID I000 Series

Страница 1: ...Compatible with VRF and Commercial lines USER MANUAL Issue date 05 2018 r1 3 ENGLISH...

Страница 2: ...ion is subject to change without notice URL https www intesis com 2 24 Modbus RTU EIA 485 Interface for Midea air conditioners Compatible with VRF and Commercial lines ORDER CODE LEGACY ORDER CODE INM...

Страница 3: ...d are only intended to help improve understanding of the functionality and handling of the product In view of the wide range of possible applications of the product and because of the many variables a...

Страница 4: ...er 9 4 2 Modbus Registers for INMBSMID001I000 9 4 2 1 Control and status registers 9 4 2 2 Configuration Registers 11 4 3 Modbus Registers for INMBSMID004I000 INMBSMID008I000 INMBSMID032I00012 4 3 1 G...

Страница 5: ...NMBSMID008I000 INMBSMID032I000 devices can be connected on the same network INMBSMID I000 is a Modbus slave device Direct connection to the Midea XYE bus Configuration from both on board DIP switches...

Страница 6: ...r of AC units to control the recommended connection methods can be seen in Figure 2 1 and Figure 2 2 NOTE If a CCM Central Controller is present in the XYE bus then the INMBSMID I000 cannot be connect...

Страница 7: ...connected Please disconnect the CCM Central Controller for use of the gateway 90 mm 3 5 MODBUS RTU EIA 485 Bus EIA485 A B X Y V1 V2 AC Unit Power 53 mm 2 1 For wall mounting extract the upper and dow...

Страница 8: ...nnect the Modbus RTU EIA 485 bus to the EIA485 A B connector of the interface 5 Connect the power cable between the interface and the Mains Power following the instructions of the diagram Screw each b...

Страница 9: ...needs to be set in the AC unit 4 2 1 Control and status registers Register Address protocol address Register Address PLC address R W Description 0 1 R W AC unit On Off 0 Off 1 On 1 2 R W AC unit Mode...

Страница 10: ...ambient temperature from external sensor at Modbus side 1 2 3 7 32768 Initialization value No temperature is being provided from an external sensor Any other C x10 C F 23 24 R AC Real temperature set...

Страница 11: ...minutes 14 15 R Modbus RTU Baud rate 2400bps 4800bps 9600bps Default Value 19200bps 38400bps 57600bps 76800bps 115200bps 15 16 R Device s Modbus Slave address 1 63 21 22 R Max number of fan speeds 49...

Страница 12: ...the interface Register Address protocol address Register Address PLC address R W Description 0 1 W AC unit On Off Global 0 Off 1 On 1 2 W AC unit Mode Global 12 0 Auto 1 Heat 2 Dry 3 Fan 4 Cool 2 3 W...

Страница 13: ...78 Initialization value 17 30 C C x10 C 63 86 F 1000 20 n 5 1000 20 n 6 R AC unit Temperature reference 16 17 18 32678 Initialization value Ranges determined by the Manufacturer of the AC indoor unit...

Страница 14: ...200 2031 2032 R Capacity 22 4 INMBSMID004I000 4 Indoor Units 8 INMBSMID008I000 8 Indoor Units 32 INMBSMID0032I000 32 Indoor Units 2040 2041 R Modbus RTU Baud rate 2400bps 4800bps 9600bps Default 19200...

Страница 15: ...unit does not allow to provide an external temperature to be used as a reference of the control loop of the AC indoor unit In order to overcome this limitation and enable the usage of an external tem...

Страница 16: ...pplied The temperature setpoint s value shown by the Remote Controller from Midea connected to the indoor unit shall show a different value from the value shown in register 4 5 Instead it shall show t...

Страница 17: ...1 AC indoor unit s features SW1 P1 4 Description AC Unit does not have AUTO mode Default value AC Unit has AUTO mode AC Unit does not have DRY mode Default value AC Unit has DRY mode AC Unit does not...

Страница 18: ...e magnitude C F and EIA 485 termination resistor Table 4 3 SW4 Temperature and termination resistor configuration SW4 P1 2 4 Description Temperature values in Modbus register are represented in degree...

Страница 19: ...Add SW3 P1 6 Add SW3 P1 6 Add SW3 P1 6 Add SW3 P1 6 Add SW3 P1 6 0 13 26 39 52 1 14 27 40 53 2 15 28 41 54 3 16 29 42 55 4 17 30 43 56 5 18 31 44 57 6 19 32 45 58 7 20 33 46 59 8 21 34 47 60 9 22 35...

Страница 20: ...ce LED indicator The device includes LED indicators to show all the possible operational states In the following table you will find the possible indication combinations and its meaning L1 green LED D...

Страница 21: ...h are listening the bus when all the transmitters outputs are in three state high impedance a fail safe biasing mechanism is required This mechanism provides a safe status a correct voltage level in t...

Страница 22: ...d or with ferrule 1 core 0 5mm2 2 5mm2 2 cores 0 5mm2 1 5mm2 3 cores not permitted Stock Humidity 95 RH non condensing Modbus RTU port 1 x Serial EIA485 Plug in screw terminal block 2 poles A B Compat...

Страница 23: ...ormation is subject to change without notice URL https www intesis com 23 24 6 List of supported AC Unit Types A list of Midea indoor unit model s references compatible with INMBSMID I000 and its avai...

Страница 24: ...ter module protection 13 EC Cooling error 14 ED Outdoor unit fault protection 15 EE Water level fault detection 16 EF Other errors 101 P0 Vaporizer temperature protection 102 P1 Thawing or cold air pr...

Отзывы: