4.3.2
Individual Control and status registers
Notice that
“
n
”
stands for the Indoor Unit
’s
index number (0..31) which by default matches
the
IU’s
physical address assigned to it (0..31). These registers apply to each indoor unit
connected to the interface.
You can change the physical address assigned to the index “n”
by writing in
register ‘
1000 + 20*n + 9
’
the value of the desired IU
’s
address (0..63).
Register Address
(protocol address)
Register Address
(PLC address)
R/W Description
(1000 + 20*n + 0)
(1000 + 20*n + 1) R/W
AC unit On/Off
▪
0: Off
▪
1: On
(1000 + 20*n + 1)
(1000 + 20*n + 2) R/W
AC unit Mode
16
▪
0: Auto (Default value)
▪
1: Heat
▪
2: Dry
▪
3: Fan
▪
4: Cool
(1000 + 20*n + 2)
(1000 + 20*n + 3) R/W
▪
0: Auto (Default value)
▪
1: SP1
▪
2: SP2
▪
3: SP3
(1000 + 20*n + 3)
(1000 + 20*n + 4) R/W
AC unit Up/Down Vane Position
▪
0: Off (Default value)
▪
10: Swing
(1000 + 20*n + 4)
(1000 + 20*n + 5) R/W
AC unit Temperature setpoint
16,17,18
▪
-32678 (Initialization value)
▪
17..30 ºC (ºC/x10ºC)
▪
63..86 ºF
(1000 + 20*n + 5)
(1000 + 20*n + 6)
R
▪
-32678 (Initialization value)
▪
Ranges determined by the Manufacturer
of the AC indoor unit. (ºC/x10ºC/ºF)
(1000 + 20*n + 6)
(1000 + 20*n + 7)
R
AC Alarm status
▪
0: No Alarm
▪
1: Alarm
(1000 + 20*n + 7)
(1000 + 20*n + 8)
R
AC Error Code
19
▪
0: No error active
▪
65535 (-1 if it is read as signed value).
Error in the communication of
INMBSMID004I000 /
INMBSMID008I000 /
INMBSMID032I000 with the AC unit
▪
Any other error present, see the table at
the end of this document.
(1000 + 20*n + 8)
(1000 + 20*n + 9) R/W
Remote lock
20,21
▪
0: Off (Default value)
▪
1: On
(1000 + 20*n + 9) (1000 + 20*n +10) R/W Indoor Unit Address assignation in n
▪
Address range: 0..63
16
Available values will depend on the AC unit mode. Check the AC unit model functions in its user manual to know the possible
values for this register.
17
Magnitude for this register can be adjusted to Celsius x 1ºC, Celsius x 10ºC (default) or Fahrenheit.
18
It is not possible turn to x10 the value shown in Fahrenheit.
19
See section 7 for possible error codes and their explanation.
20
This value is stored in a non-volatile memory
21
This register blocks the
Remote Controller’s
communication installed in the MD-RC bus (if this one has been installed).