User’s Manual r
1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
11 / 24
4.2.2 Configuration Registers
Register Address
(protocol address)
Register Address
(PLC address)
R/W Description
13
14
R/W
“Open Window” switch
-off timeout
10
▪
0..30 (minutes)
▪
Factory setting: 30 (minutes)
14
15
R
Modbus RTU Baud rate
▪
2400bps
▪
4800bps
▪
9600bps (Default Value)
▪
19200bps
▪
38400bps
▪
57600bps
▪
76800bps
▪
115200bps
15
16
R
Device's Modbus Slave address
▪
1..63
21
22
R
Max number of fan speeds
49
50
R
Device ID: 0x2200
50
51
R
Software version
99
100
W
Reset/Reboot device
▪
1: Reset
2031
2032
R
Capacity
11
▪
1: INMBSMID001I000 (1 Indoor Unit)
10
Once window contact is open, a count-down to switch off the AC Unit will start from this configured value.
11
The value of this register depends on the N value (being N the number of max. indoor units that admits INMBSMID---I000)