Communication type
: Select if ASCII communication will be through TCP/IP, serial (EIA232 or EIA485) or
both.
•
Notification on ASCII Value:
Gateway will allow sending spontaneous messages to the ASCII bus when a
change of value is received in the BACnet side.
•
Answer required for write commands:
If enabled, the gateway will send back an OK message to the ASCII
master device.
•
Define custom string commands:
Define the special character to be used to read or write the internal gateway
datapoint.
•
Port:
TCP port to be used for the ASCII communication. By default, it is set to 5000.
•
Keep Alive:
Time of inactivity before sending a keep alive message.
o
0:
Disabled
o
1
…1440:
Possible values expressed in minutes. By default, it is set to 10.
•
Connection type
: Physical connection, between EIA232 and EIA485 can be selected.
•
Baud rate:
Selectable from 1200, 2400, 4800, 9600, 19200, 38400, 56700 and 115200.
•
Data type:
o
Data Bits: 8
o
Parity can be selected from: none, even, odd.
o
Stop Bits:1 and 2
5.2.3.2 BACnet Client Configuration
Set the parameters for connection to BACnet network / BACnet server devices in the network.
Figure 5.4
Intesis MAPS configuration tab for BACnet Client