Figure 4.4
Mitsubishi Heavy Industries interface configuration
1.
Devices:
In this list, you can individually enable each of the 128 indoor units
available on the system. The index in the column “Indoor unit” (i.e. the number x
in “
Indoor Unit
xxx”) is the reference that will be used later on (in tab “Signals”)
to refer to this AC indoor unit. You can also change the name of the indoor Unit to
facilitate integration tasks.
2.
Gateway version:
Selection of the
Intesis Modbus Server
–
Mitsubishi Heavy
Industries
gateway you are setting up. (
128AC
for
INMBSMHI128O000,
48AC
for
INMBSMHI048O000
)
3.
Timeout response:
Maximum amount of time permitted before activating the
Communication Error signal. It is expressed in milliseconds (ms) and ranges can
vary from 2000 ms to 10000 ms.
4.
Delay interframe:
Maximum amount of time permitted between End Of
Transmission (EOT) and a new frame. It is expressed in milliseconds (ms) and
ranges can vary from 500 ms to 3000 ms.
5.
Monitoring cadence:
Cadence of monitoring and subscription. It is expressed in
seconds (s) and ranges can vary from 60 s to 600 s.
Additional configuration parameters should generally be left to their default value. They only
might need to be tuned in some very specific cases (installations with large number of units,
scenarios with large bursts of commands sent at
once …)
4.2.2
Modbus map
tab
In order to know the Modbus map that is going to be used by the interface, the
Modbus
map
tab can be consulted.
1
2
3
4
5