Intesis
TM
Modbus Server
– DALI
User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL
http
s
://www.intesis.com
15 / 39
Modbus Address
First Address is 0
Ballast /
Device type
Read/
Write
Register/signal name
Possible values
FL
E
M
L
L
E
D
7000 x c (100 x sa)
+ 67
x
W
Reset Duration Test Done Flag
1-Reset Duration Flag
7000 x c (100 x sa)
+ 68
x
W
Reset Lamp Time
1-Lamp Emergency Time Reset
7000 x c (100 x sa)
+ 69
x
R/W Store Test Execution Timeout
0 to 255 days
7000 x c (100 x sa)
+ 70
x
R/W Store Prolong Time
0 to 127,5 minutes
7000 x c (100 x sa)
+ 71
x
R/W Store Function Test Interval
0-Disabled, 1 to 255 days
7000 x c (100 x sa)
+ 72
x
R/W Store Duration Test Interval
0-Disabled, 1 to 97 weeks
7000 x c (100 x sa)
+ 73
x
R/W Store Emergency Level
0 to 100 %
7000 x c (100 x sa)
+ 74
R
Not used
Default to 0
7000 x c (100 x sa)
+ 75
R
Not used
Default to 0
7000 x c (100 x sa)
+ 76
R
Not used
Default to 0
7000 x c (100 x sa)
+ 77
R
Not used
Default to 0
7000 x c (100 x sa)
+ 78
R
Not used
Default to 0
7000 x c (100 x sa)
+ 79
R
Not used
Default to 0