Intesis
TM
Modbus Server
– DALI
User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL
http
s
://www.intesis.com
13 / 39
Modbus Address
First Address is 0
Ballast /
Device type
Read/
Write
Register/signal name
Possible values
FL
E
M
L
L
E
D
7000 x c (100 x sa)
+ 42
x
R
Failure Status
b7-FunctFail, b6-DurFail, b5-DurTestDelay, b4-
FunctTestDelay, b3-EmLampFail, b2-BattFail, b1-
BattDurFail, b0-CircFail
7000 x c (100 x sa)
+ 43
x
R
Emergency Mode
b7-HardSwOn, b6-HardInhibit, b5-DurTestProg, b4-
FunctTestProg, b3-ExtdEmMode, b2-EmMode, b1-
NormMode, b0-RestMode
7000 x c (100 x sa)
+ 44
x
R
Emergency Status
b7-PhysicSel, b6-Ident, b5-DurTestPend, b4-
FunctTestPend, b3-BattFull, b2-DurTestDone, b1-
FunctTestDone, b0-InhibitMode
7000 x c (100 x sa)
+ 45
x
R
Emergency Battery Charge
0 to 100 %
7000 x c (100 x sa)
+ 46
x
R
Next Function Test
0 to 16384 hours
7000 x c (100 x sa)
+ 47
x
R
Next Duration Test
0 to 16384 hours
7000 x c (100 x sa)
+ 48
x
R
Function Test Interval
0-Disabled, 1 to 255 days
7000 x c (100 x sa)
+ 49
x
R
Duration Test Interval
0-Disabled, 1 to 97 weeks
7000 x c (100 x sa)
+ 50
x
R
Test Execution Timeout
0 to 255 days
7000 x c (100 x sa)
+ 51
x
R
Prolong Time
0 to 127,5 minutes
7000 x c (100 x sa)
+ 52
x
R
Duration Test Result
0 to 510 minutes
7000 x c (100 x sa)
+ 53
x
R
Lamp Total Operation Time
0 to 1016 hours