Intesis
TM
KNX
– DALI
User Manual r1.1 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL
http
s
://www.intesis.com
9 / 34
x
x
x Device Type
1 byte
Unsigned Value
5.x
T
R
0-Fluorescent
1-Emergency
2 Discharge
3-Halogen
4-Incandescent
5-Digital signal
6-LED
7-Switching
8-Colour Control
x
x
x Physical Minimum Level
1 byte
DPT_Scaling
5.001
T
R
0 to 100 %
x
x
x Min Level
1 byte
DPT_Scaling
5.001
T
R
0 to 100 %
x
x
x Max Level
1 byte
DPT_Scaling
5.001
T
R
0 to 100 %
x
x
x Power On Level
1 byte
DPT_Scaling
5.001
T
R
0 to 100 %
x
x
x System Failure Level
1 byte
DPT_Scaling
5.001
T
R
0 to 100 %
x
x
x Fade Time
1 byte
Unsigned Value
5.x
T
R
0 to 15
x
x
x Fade Rate
1 byte
Unsigned Value
5.x
T
R
1 to 15
x
x
x Arc Power Level
1 byte
DPT_Scaling
5.001
U
Ri
W
R
0 to 100 %
x
x
x Arc Power Off / On
1 bit
DPT_Switch
1.001
U
Ri
W
R
0-Off; 1-100 %
x
x
x Step Down / Up
1 bit
DPT_Step
1.007
U
Ri
W
R
0-Step Down, 1-Step Up
x
x
x Recall Min Level
1 bit
DPT_Start
1.010
U
Ri
W
R
1-Recall Min Level
x
x
x Recall Max Level
1 bit
DPT_Start
1.010
U
Ri
W
R
1-Recall Max Level
x
x
x Go to Scene
1 byte
Unsigned Value
5.x
U
Ri
W
R
0 to 15