background image

Ewon Cosy 131

INSTALLATION GUIDE

IG-0022-00 2.8 en-US ENGLISH

Содержание Ewon Cosy 131

Страница 1: ...Ewon Cosy 131 INSTALLATION GUIDE IG 0022 00 2 8 en US ENGLISH...

Страница 2: ...e range of possible applications of the product and because of the many variables and requirements associated with any particular implementation HMS Industrial Networks cannot assume responsibility or...

Страница 3: ...ctives Standards and Compliance 5 3 4 Field Implementation Environmental Conditions 6 3 5 Internal Battery 10 4 Hardware Description 11 4 1 Label 11 4 2 Mechanical Dimensions 13 4 3 Overall Descriptio...

Страница 4: ...on Cosy 131 Installation Guide IG 0022 00 2 8 en US B Specification of the External Power Supply 26 C Digital Output Digital Inputs 27 C 1 Possible Features 28 D Supported Wireless Wi Fi Frequencies 2...

Страница 5: ...pplicable Safety Standards p 5 2 0 2018 03 02 Modified Picture in Digital Output Digital Inputs p 27 2 1 2018 04 17 Added 4G models EU NA 2 2 2018 05 03 Modified Safety Environmental Regulatory Inform...

Страница 6: ...or USB devices using Talk2M connection as an industrial VPN router The Ewon Cosy 131 should not be used as a pure Ethernet switch 2 4 Type Part Numbers The Ewon Cosy 131 is tagged following these par...

Страница 7: ...with the CE RE directives and the FCC regulations related to the wireless modems It also belongs to Class A Information Technology Equipment ITE In a domestic environment this product may cause radio...

Страница 8: ...This equipment is not suitable for use in locations where children are likely to be present 3 4 2 Ingress Protection The Ewon Cosy 131 has an IP20 protection grade Therefore the Ewon Cosy 131 is NOT s...

Страница 9: ...Safety Environmental Regulatory Information 7 30 Fig 1 DIN rail mounting position Description 1 SIM card slot 2 DIN rail mounting bracket Ewon Cosy 131 Installation Guide IG 0022 00 2 8 en US...

Страница 10: ...mm Caution Please set the screws in both wall mounting brackets to prevent accidents To ensure a proper ventilation of the equipment a free gap of at least 2 cm must be respected in front of all uppe...

Страница 11: ...er contact 0 5A or better Caution To prevent accidentally pulling out wires be sure that cables are firmly attached to wire connectors For screw connectors make sure that screws are properly tightened...

Страница 12: ...for Ethernet and USB to comply with the EMC requirements 3 5 Internal Battery The Ewon Cosy 131 contains a CR2032 battery This battery is used to maintain the real time clock up to date even when the...

Страница 13: ...uction WW Week of production SSSS Sequential manufacturing order PP Product type MAC MAC address of the Ethernet adapter Rating Power supply requirements Marks CE UL logos if applicable The applicable...

Страница 14: ...form 6 Cosy 131 platform 1 Communication options 1 1 1 Ethernet 3 Communication options 2 3 3 Ethernet 3 Field communication option 3 USB m Modem communication option 0 No modem C Wi Fi D 3G modem E F...

Страница 15: ...ons of the Ewon Cosy 131 4 3 Overall Description 4 3 1 Front Fig 6 Front panel Description 1 Reset button 2 Status LEDs 3 LAN WAN Ethernet ports and corresponding status LEDs Red WAN and Green LAN 4 U...

Страница 16: ...al IN 1 See Digital Output Digital Inputs p 27 Green ON Signal on Input 1 detected DI2 Digital IN 2 See Digital Output Digital Inputs p 27 Green ON Signal on Input 2 detected T2M Talk2M See Digital Ou...

Страница 17: ...131 with Internal Wi Fi Model EC6133C_00MA Item Value s Protocols and frequencies IEEE802 11b g n 2 4GHz Channels 1 to 11 inclusive Antenna connector Type RP SMA Antenna included in the delivery Chara...

Страница 18: ...n in Mounting Recommendations p 6 SIM card tray is located at the rear of the Ewon Cosy 131 Additional information The product complies with the RE directive the FCC the IC and Japan regulations relat...

Страница 19: ...s been performed with the reference antenna Taoglass G 30 B108111 4 As seen in Mounting Recommendations p 6 SIM card tray is located at the rear of the Ewon Cosy 131 Additional information The product...

Страница 20: ...manual tightening is sufficient Device conformity assessment has been performed with the reference antenna Taoglass G 30 B108111 5 As seen in Mounting Recommendations p 6 SIM card tray is located at...

Страница 21: ...wrench a soft manual tightening is sufficient Device conformity assessment has been performed with the reference antenna Panorama B4BE 7 27 6 As seen in Mounting Recommendations p 6 SIM card tray is...

Страница 22: ...odems Absolute maximum antenna gain as per FCC s rules and regulations 47 CFR Part 22H 5 22dBi Part 27 3 31dBi Part 24E 6 45dBi Modifications cannot be made by the user if it influences the normal beh...

Страница 23: ...ill be configured as follows Port 1 LAN Port 2 LAN Port 3 LAN Port 4 WAN The Ethernet ports functionality can be configured as wanted except for the port 1 which always remains in LAN mode Ethernet po...

Страница 24: ...rt Connect a LAN port port 1 is always set as a LAN port of the Ewon Cosy 131 to one s computer either through a point to point connection or a network where there is no risk Cosy 131 s default IP add...

Страница 25: ...for approximately 30 seconds until the USR LED blinks red 1x per second If it isn t released at that specific moment a second level reset phase is initiated The LED labeled BI1 turns off Wait approxim...

Страница 26: ...ror pattern occurs on the USR LED please check out the troubleshooting page www ewon biz support 6 3 Impact Matrix of a Reset Reset level Erased or Reset Preserved Impact of a reset level 1 User reset...

Страница 27: ...bsence of a torque wrench a soft manual tightening is sufficient Fig 12 Connector pinout PIN ICON ID Description 1 O DO_COM Output signal 0V ground connected to the emitter of the MOSFET transistor 2...

Страница 28: ...min Certified for 70 C and for altitudes up to 2000m The safety LPS power supply is not part of the delivery Suggested power supply SIEMENS SITOP logo power 24V 2 5A 60W Siemens order ref 6EP1332 1SH4...

Страница 29: ...pler The maximum current flow inside this transistor has a value above the one specified in the Cosy 131 in order to cope with the switching power losses The transistor used is in an open drain type w...

Страница 30: ...ernet connection Authorize or prevent the VPN connection Trigger an SMS or email notification DI2 DI2 Trigger an SMS or email notification T2M DO Can be wired to an external device to propagate the Ta...

Страница 31: ...D Supported Wireless Wi Fi Frequencies Fig 15 Supported Wi Fi frequencies Supported channels frequencies are between channel 1 2 412 Ghz and channel 11 2 462 Ghz Channels 12 13 14 are not supported E...

Страница 32: ...last page 2020 HMS Industrial Networks Box 4126 300 04 Halmstad Sweden info hms se IG 0022 00 2 8 en US 2020 01 20 16782...

Отзывы: