7.10.8
Data Exchange Control
By default Data exchange control is disabled.
When Data exchange control is enabled, the first four bytes of process data on the Modbus TCP
network contain the data exchange control.
The Data exchange control holds 32 bits.
Each bit in the Data exchange control can be used to enable/disable data exchange for individual
nodes on the subnetwork.
If control bit does not correspond to a configured node, the control bit is ignored. For example,
this occurs when the number of configured nodes is less than 32.
When the data exchange is enabled for the corresponding node, the control bit is 1.