77 (124)
7.10.6
Offline Option
Offline mode is used to define what data to send if the network connection or connection with a
specific node is lost.
You must specify the offline mode to use for each transaction on the I/O data map.
Select one of the following Offline options:
•
Clear (Default): The data is cleared and the value 0 is sent.
•
Freeze: The Communicator holds the value until the connection is restored.
•
No scanning: Stop sending this transaction on the sub-network. This option is only valid for
produce and request transactions.
Anybus
®
Communicator
™
User Manual