HK Instruments DPT-PRIIMA-MOD Series Скачать руководство пользователя страница 4

Copyright HK Instruments 2022

www.hkinstruments.fi

Installation version 1.0 2022

The seller is obligated to provide a warranty of five years for the deliv-
ered goods regarding material and manufacturing. The warranty period 
is considered to start on the delivery date of the product. If a defect 
in raw materials or a production flaw is found, the seller is obligated, 
when the product is sent to the seller without delay or before expira-
tion of the warranty, to amend the mistake at his/her discretion either 
by repairing the defective product or by delivering free of charge to 
the buyer a new flawless product and sending it to the buyer. Delivery 
costs for the repair under warranty will be paid by the buyer and the 
return costs by the seller. The warranty does not comprise damages 
caused by accident, lightning, flood or other natural phenomenon, nor-
mal wear and tear, improper or careless handling, abnormal use, over-
loading, improper storage, incorrect care or reconstruction, or changes 
and installation work not done by the seller. The selection of materi-
als for devices prone to corrosion is the buyer’s responsibility, unless 
otherwise  is  legally  agreed  upon.  Should  the  manufacturer  alter  the 
structure of the device, the seller is not obligated to make comparable 
changes to devices already purchased. Appealing for warranty requires 
that the buyer has correctly fulfilled his/her duties arisen from the de-
livery and stated in the contract. The seller will give a new warranty for 
goods that have been replaced or repaired within the warranty, how-
ever only to the expiration of the original product’s warranty time. The 
warranty includes the repair of a defective part or device, or if needed, 
a new part or device, but not installation or exchange costs. Under no 
circumstance is the seller liable for damages compensation for indirect 
damage.

2) Manual Pushbutton zero point calibration

NOTE: Supply voltage must be connected at least one hour prior to 
zero point adjustment.

a) Disconnect both pressure tubes from the pressure ports l 

and –.

b) Push down the zero button until the LED light (red) turns on and 

the display reads “zeroing” (display option only). (see figure 3)

c) The zeroing of the device will proceed automatically in 4 seconds. 

Zeroing is complete when the LED turns off, and the display reads 
0 (display option only).

d) Reinstall the pressure tubes ensuring that the High pressure tube 

is connected to the port l, and the Low pressure tube is 
connected to the port labeled −.

3) Via Modbus register

Make sure there is no pressure in the duct when the zeroing is done 
via Modbus register.

b) Push down the zero button (joystick) until the LED light (red) 
turns on and the display reads “zeroing” (display option only). (see 
Figure 6)
c) The zeroing of the device will proceed automatically.  Zeroing is 
complete when the LED turns off, and the display reads 0 (display 
option only).  
d) Reinstall the pressure tubes, ensuring the High pressure tube is 
connected to the port l, and the Low pressure tube is 
connected to the port labeled −.

Press down button

LED turns ON

Display reads “Zeroing”

LED

Figure 3

ZEROING THE DEVICE 

CONTINUED

STEP 5: MODBUS REGISTERS

Register

Parameter description

Data Type

Value

Range

3x0001

Program version

16 bit 

0...9900

0,00...99,00

3x0002

Pressure reading Pa

16 bit

-24900...24900 *

± 2490.0 Pa

3x0003

Pressure reading kPa

16 bit

-24900...24900 *

± 2.4900 kPa

3x0004

Pressure reading mbar

16 bit

-24900...24900 *

± 24.900 Pa

3x0005

Pressure reading mmWC

16 bit

-25400...25400 *

± 253.91 mmWC

3x0006

Pressure reading inWC

16 bit

-10000...10000 *

± 10.000 inWC

3x0007

Pressure reading psi

16 bit

-3610...3610 *

± 0.3611 psi

3x0008

Flow m3/s

16 bit

0...10000

0...100 m3/s

3x0009

Flow m3/h

16 bit

0...30000

0...30000 m3/h

3x0010

Flow cfm

16 bit

0...30000

0...30000 cfm

3x0011

Flow l/s

16 bit

0...3000

0...3000 l/s

3x0012

Velocity m/s

16 bit

0...1000

0...100 m/s

3x0013

Velocity f/min

16 bit

0...5000

0...5000 f/min

Function code 04 - Read input register

MODBUS REGISTERS

 CONTINUED

Function code 05 - Write single coil

Register

Parameter description

Data Type

Value

Range

0x0001

Zero point calibration

Bit 0

0...1

On - Off 

WARRANTY POLICY

RECYCLING/DISPOSAL

The  parts  left  over  from  installation  should  be 
recycled  according  to  your  local  instructions. 
Decommissioned  devices  should  be  taken  to  a 
recycling site that specializes in electronic waste.

*) The value and range are determined by the selected pressure range ±120 Pa, ±240 Pa, ±620 Pa, 
±1240 Pa, ±2490 Pa. The values shown in the table when the largest area is selected.

Function code 03 - Read input holding register, Function code 06 - 
Write single register, Function code 16 - Write multiple registers

Register

Parameter description

Data Type

Value

Range

4x0001

Manufacturer

16 bit 

0...8

0=Fläkt Woods, 1=Rosenberg,
2=Nicotra-Gebhardt, 3=Comefri,
4=Ziehl, 5=ebm-papst, 6=Gebhardt,
7=Nicotra, 8=Common probe

4x0002

Formula unit (if manufacturer
selection = common probe)

16 bit

0...5

0: m3/s, 1: m3/h, 2: cfm, 3: l/s, 
4: m/s, 5: f/min

4x0003

K-factor integer

16 bit

0...9999

0...9999

4x0004

K-factor decimal

16 bit

0...999 

0...999

4x0005

Response time

16 bit

0...20 

0=0.4 s, 1=1 s, 2=2 s...20=20 s

4x0006

Pressure Range

16 bit

0...4

0=±120 Pa, 1=±240 Pa, 2=±620 Pa,
3=±1240 Pa, 4=±2490 Pa

Содержание DPT-PRIIMA-MOD Series

Страница 1: ...pe monitoring pressure and flow SPECIFICATIONS Performance Measurement ranges 120 Pa 240 Pa 620 Pa 1240 Pa 2490 Pa selectable via menu or modbus default range Accuracy at applied pressure 0 4 0 4 Pa Including general accuracy linearity hysteresis long term stability and repetition error Overpressure Proof pressure 10 kPa Burst pressure 30 kPa Zero point calibration Automatic autozero manual pushbu...

Страница 2: ...and route the cable through the strain relief and connect the wires to the terminal block s see step 2 3 The device is now ready for configuration WARNING Apply power only after the device is properly wired STEP 2 WIRING DIAGRAMS For CE compliance a properly grounded shielding cable is required 1 Unscrew the strain relief and route the cable 2 Connect the wires as shown in figure 2 3 Tighten the s...

Страница 3: ...9999 000 K VALUE 9000 000 SELECT UP DOWN 9 Select the address for Modbus 1 247 10 Select the baud rate 9600 19200 38400 ADDRESS 99 SELECT UP DOWN BAUD RATE 9600 SELECT UP DOWN 11 Select the parity bit None Even Odd PARITY BIT NONE SELECT UP DOWN STEP 4 ZEROING THE DEVICE NOTE Always zero the device before use To zero the device three options are available 1 Autozero calibration manual zeroing not ...

Страница 4: ...nected to the port labeled 3 Via Modbus register Make sure there is no pressure in the duct when the zeroing is done via Modbus register b Push down the zero button joystick until the LED light red turns on and the display reads zeroing display option only see Figure 6 c The zeroing of the device will proceed automatically Zeroing is complete when the LED turns off and the display reads 0 display ...

Отзывы: