DPT

SCHEMATICS

DIMENSIONAL DRAWINGS

Figure 1a - Surface mounting

MOUNTING THE DEVICE 

CONTINUED

Figure 1b - Mounting orientation

Figure 1c - Application connections

Connection for display

Terminal block

Menu buttons

ZERO

A

24 V

GND

SELECT

UP

DOWN

B

A

B

Pressure sensor

Led

DPT

4.3

The pressure tubes are connected to a flow measurement probe (i.e. FloXact), or to the 
measurement ports specified by the fan manufacturer. Please see the FloXact installation 
guide or the fan manufacturer’s technical specifications for more information.

YES

NO

NO

INSTALLATION

1) Mount the device in the desired location (see step 1).
2) Open the lid and route the cable through the strain relief and 

connect the wires to the terminal block(s) (see step 2).

3) The device is now ready for configuration.

 

  WARNING! Apply power only after the device is properly wired.

STEP 2: WIRING DIAGRAMS

For CE compliance, a properly grounded shielding cable is required.
1) Unscrew the strain relief and route the cable. 
2) Connect the wires as shown in figure 2.
3) Tighten the strain relief.

It is recommended to use shielded twisted pair cable for Modbus cabling. 
The cable shield must be earthed only in one point, normally, at the end of 
the main cable.

Figure 2 - Wiring diagram

B

A

24 V

GND

+ Power supply

24 VDC / 24 VAC

Modbus

STEP 1: MOUNTING THE DEVICE

1) Select the mounting location (duct, wall, panel).
2) Use the device as a template and mark the screw holes.
3) Mount with appropriate screws.

Pressure

Flow

Static pressure

Filter/Damper

monitoring

Fan/Blower

monitoring

Not

connected

Содержание DPT-PRIIMA-MOD Series

Страница 1: ...pe monitoring pressure and flow SPECIFICATIONS Performance Measurement ranges 120 Pa 240 Pa 620 Pa 1240 Pa 2490 Pa selectable via menu or modbus default range Accuracy at applied pressure 0 4 0 4 Pa Including general accuracy linearity hysteresis long term stability and repetition error Overpressure Proof pressure 10 kPa Burst pressure 30 kPa Zero point calibration Automatic autozero manual pushbu...

Страница 2: ...and route the cable through the strain relief and connect the wires to the terminal block s see step 2 3 The device is now ready for configuration WARNING Apply power only after the device is properly wired STEP 2 WIRING DIAGRAMS For CE compliance a properly grounded shielding cable is required 1 Unscrew the strain relief and route the cable 2 Connect the wires as shown in figure 2 3 Tighten the s...

Страница 3: ...9999 000 K VALUE 9000 000 SELECT UP DOWN 9 Select the address for Modbus 1 247 10 Select the baud rate 9600 19200 38400 ADDRESS 99 SELECT UP DOWN BAUD RATE 9600 SELECT UP DOWN 11 Select the parity bit None Even Odd PARITY BIT NONE SELECT UP DOWN STEP 4 ZEROING THE DEVICE NOTE Always zero the device before use To zero the device three options are available 1 Autozero calibration manual zeroing not ...

Страница 4: ...nected to the port labeled 3 Via Modbus register Make sure there is no pressure in the duct when the zeroing is done via Modbus register b Push down the zero button joystick until the LED light red turns on and the display reads zeroing display option only see Figure 6 c The zeroing of the device will proceed automatically Zeroing is complete when the LED turns off and the display reads 0 display ...

Отзывы: