INSTALLATION
INSTRUCTIONS

DIFFERENTIAL PRESSURE TRANSMITTERS 
DPT-Priima-MOD Series

•  READ THESE INSTRUCTIONS CAREFULLY BEFORE 

ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS 
DEVICE.

•  Failure to observe safety information and comply with 

instructions can result in PERSONAL INJURY, DEATH AND/OR 

PROPERTY DAMAGE.

•  To avoid electrical shock or damage to equipment, disconnect 

power before installing or servicing and use only wiring with 
insulation rated for full device operating voltage.

•  To avoid potential fire and/or explosion do not use in potentially 

flammable or explosive atmospheres.

•  Retain these instructions for future reference.
•  This product, when installed, will be part of an engineered 

system whose specifications and performance characteristics 
are not designed or controlled by HK Instruments. Review 
applications and national and local codes to assure that the 
installation will be functional and safe. Use only experienced and 
knowledgeable technicians to install this device.

Thank you for choosing an HK Instruments DPT-Priima-MOD series 
transmitter. DPT-Priima-MOD is a multifunctional high accuracy trans-
mitter for measuring volume flow, velocity, and static and differential 
pressure. It is designed for cleanrooms and other demanding applica-
tions. The measurements can be read and the configuration done via 
Modbus communication. DPT-Priima-MOD can also be used with sev-
eral different measurement probes such as FloXact™ or pitot tube, and 
air dampers.

DPT-Priima-MOD models come with a local display and an automatic 
zero point calibration. Calibration certificate available as an option.

DPT-Priima-MOD is commonly used in applications requiring high
measurement accuracy:
• monitoring pressure in cleanrooms
• monitoring pressure difference across the building envelope
• monitoring pressure and flow

SPECIFICATIONS

Performance

Measurement ranges:

±120 Pa*, ±240 Pa, ±620 Pa, ±1240 Pa, ±2490 Pa

(selectable via menu or modbus)

*default range

Accuracy (at applied pressure):

0.4 % ±0.4 Pa

(Including: general accuracy, linearity, hysteresis, long 

term stability, and repetition error)

Overpressure:

Proof pressure: 10 kPa

Burst pressure: 30 kPa

Zero point calibration:

Automatic autozero, manual pushbutton or via Modbus 

register

Response time:

0.4−20 s, selectable via menu or via Modbus register

(63 % of the change)

Communication

Protocol: MODBUS over Serial Line

Transmission Mode: RTU

Interface: RS485

Byte format (11 bits) in RTU mode:

 

Coding System: 8-bit binary

 

Bits per Byte:

 

 

1 start bit

 

 

8 data bits, least significant bit sent  

 

 

first

 

 

1 bit for parity

 

 

1 stop bit

Baud rate: selectable in configuration

Modbus address: 1−247 addresses selectable in

configuration menu 

Technical Specifications

Media compatibility:

Dry air or non-aggressive gases

Pressure units (select via menu):

Pa, kPa, mbar, inWC, mmWC, psi

Flow units (select via menu):

Volume: m

3

/s, m

3

/h, cfm, l/s

Velocity: m/s, ft/min 

Measuring element:

MEMS, no flow-through

Environment:

Operating temperature: -5...50 °C

Temperature compensated range  0...50 °C

Storage temperature: -40...70 °C

Humidity: 0 to 95 % rH, non condensing

Physical

Dimensions: 

Case: 102.0 x 71.5 x 36.0 mm

Weight: 

150 g

Mounting:

2 each 4.3 mm screw holes, one slotted

Materials:

Case: ABS

Lid: PC

Pressure fittings: Brass

Tubing: Silicone

Protection standard:

IP54 

Display

2-line display (12 characters/line)

 

Line 1: Volume or velocity measurement

 

Line 2: Pressure measurement

Size: 46.0 x 14.5 mm

Electrical connections:

4-screw terminal block

Wire: 0.2–1.5 mm

2

 (16–24 AWG)

Cable entry:

Strain relief: M16

Knockout : 16 mm

Pressure fittings

Male ø 5.2 mm

+ High pressure

- Low pressure

Electrical

Supply voltage: 

24 VAC or VDC ± 10 %

Power consumption:

< 1 W

< 2.2 W during AZ-calibration

Output signal:

via Modbus

Conformance

Meets requirements for:

 

 

CE:   

UKCA:

EMC: 

 

2014/30/EU 

S.I. 2016/1091

RoHS:   

2011/65/EU 

S.I. 2012/3032

WEEE:   

2012/19/EU 

S.I. 2013/3113

APPLICATIONS

INTRODUCTION

WARNING

RoHS

COMPLIANT

Содержание DPT-PRIIMA-MOD Series

Страница 1: ...pe monitoring pressure and flow SPECIFICATIONS Performance Measurement ranges 120 Pa 240 Pa 620 Pa 1240 Pa 2490 Pa selectable via menu or modbus default range Accuracy at applied pressure 0 4 0 4 Pa Including general accuracy linearity hysteresis long term stability and repetition error Overpressure Proof pressure 10 kPa Burst pressure 30 kPa Zero point calibration Automatic autozero manual pushbu...

Страница 2: ...and route the cable through the strain relief and connect the wires to the terminal block s see step 2 3 The device is now ready for configuration WARNING Apply power only after the device is properly wired STEP 2 WIRING DIAGRAMS For CE compliance a properly grounded shielding cable is required 1 Unscrew the strain relief and route the cable 2 Connect the wires as shown in figure 2 3 Tighten the s...

Страница 3: ...9999 000 K VALUE 9000 000 SELECT UP DOWN 9 Select the address for Modbus 1 247 10 Select the baud rate 9600 19200 38400 ADDRESS 99 SELECT UP DOWN BAUD RATE 9600 SELECT UP DOWN 11 Select the parity bit None Even Odd PARITY BIT NONE SELECT UP DOWN STEP 4 ZEROING THE DEVICE NOTE Always zero the device before use To zero the device three options are available 1 Autozero calibration manual zeroing not ...

Страница 4: ...nected to the port labeled 3 Via Modbus register Make sure there is no pressure in the duct when the zeroing is done via Modbus register b Push down the zero button joystick until the LED light red turns on and the display reads zeroing display option only see Figure 6 c The zeroing of the device will proceed automatically Zeroing is complete when the LED turns off and the display reads 0 display ...