HK Instruments DPT-MOD Series Скачать руководство пользователя страница 4

Copyright HK Instruments 2020

www.hkinstruments.fi

Installation version 7.0 2020

The seller is obligated to provide a warranty of five years for the delivered 
goods regarding material and manufacturing. The warranty period is con-
sidered to start on the delivery date of the product. If a defect in raw mate-
rials or a production flaw is found, the seller is obligated, when the product 
is sent to the seller without delay or before expiration of the warranty, to 
amend the mistake at his/her discretion either by repairing the defective 
product or by delivering free of charge to the buyer a new flawless product 
and sending it to the buyer. Delivery costs for the repair under warranty 
will be paid by the buyer and the return costs by the seller. The warranty 
does not comprise damages caused by accident, lightning, flood or other 
natural phenomenon, normal wear and tear, improper or careless handling, 
abnormal use, overloading, improper storage, incorrect care or reconstruc-
tion,  or  changes  and  installation  work  not  done  by  the  seller  or  his/her 
authorized representative. The selection of materials for devices prone to 
corrosion  is  the  buyer’s  responsibility,  unless  otherwise  is  legally  agreed 
upon. Should the manufacturer alter the structure of the device, the seller 
is not obligated to make comparable changes to devices already purchased. 
Appealing for warranty requires that the buyer has correctly fulfilled his/
her duties arisen from the delivery and stated in the contract. The seller will 
give a new warranty for goods that have been replaced or repaired within 
the warranty, however only to the expiration of the original product’s war-
ranty time. The warranty includes the repair of a defective part or device, 
or if needed, a new part or device, but not installation or exchange costs. 
Under no circumstance is the seller liable for damages compensation for 
indirect damage.

2) Autozero calibration
If  the  device  includes  the  optional  autozero  circuit,  no  action  is  re-
quired.

Autozero calibration (-AZ) is an autozero function in the form of an 
automatic zeroing circuit built into the PCB board. The autozero cali-
bration  electronically  adjusts  the  transmitter  zero  at  predetermined 
time intervals (every 10 minutes). The function eliminates all output 
signal drift due to thermal, electronic or mechanical effects, as well as 
the need for technicians to remove high and low pressure tubes when 
performing initial or periodic transmitter zero point calibration. The 
autozero adjustment takes 4 seconds after which the device returns to 
its normal measuring mode. During the 4 second adjustment period, 
the output and display values will freeze to the latest measured value. 

Transmitters  equipped  with  the  autozero  calibration  are  virtually 
maintenance free.

3) Via Modbus register
Make sure there is no pressure in the duct when the zeroing is done 
via Modbus register.

a) Disconnect both pressure tubes from the pressure ports l 
and –.

b) Push down the zero button (joystick) until the LED light (red) 
turns on and the display reads “zeroing” (display option only). (see 
Figure 6)
c) The zeroing of the device will proceed automatically.  Zeroing is 
complete when the LED turns off, and the display reads 0 (display 
option only).  
d) Reinstall the pressure tubes, ensuring the High pressure tube is 
connected to the port l, and the Low pressure tube is 
connected to the port labeled −.

Press down button

LED turns ON

Display reads “Zeroing”

LED

Figure 3

ZEROING THE DEVICE 

CONTINUED

STEP 5: MODBUS REGISTERS

Register

Parameter description

Data Type

Value

Range

3x0001

Program version

16 bit 

0...9900

0,00...99,00

3x0002

Pressure reading

16 bit

-250...2500/7000

-250...2500/7000 Pa

3x0003

Flow m3/s

16 bit

0...10000

0...100 m3/s

3x0004

Flow m3/h

16 bit

0...30000

0...30000 m3/h

3x0005

Flow cfm

16 bit

0...30000

0...30000 cfm

3x0006

Flow l/s

16 bit

0...3000

0...3000 l/s

3x0007

Velocity m/s

16 bit

0...1000

0...100 m/s

3x0008

Velocity f/min

16 bit

0...5000

0...5000 f/min

Function code 04 - Read input register

MODBUS REGISTERS

 CONTINUED

Function code 06 - Write single register

Register

Parameter description

Data Type

Value

Range

4x0001

Manufacturer

16 bit 

0...7

0...7

4x0002

Formula unit (Manufacturer=7)

16 bit

0...5

0: m3/s, 1: m3/h, 2: cfm, 3: l/s, 

4: m/s, 5: f/min

4x0003

K-factor integer

16 bit

0...9999

0...9999

4x0004

K-factor decimal

16 bit

0...999 

0...999

4x0005

Response time

16 bit

1...20 

1...20 s

Function code 16 - Write multiple registers

Register

Parameter description

Data Type

Value

Range

4x0001

Manufacturer

16 bit 

0...7

0...7

4x0002

Formula unit (Manufacturer=7)

16 bit

0...5

0: m3/s, 1: m3/h, 2: cfm, 3: l/s, 

4: m/s, 5: f/min

4x0003

K-factor integer

16 bit

0...9999

0...9999

4x0004

K-factor decimal

16 bit

0...999 

0...999

4x0005

Response time

16 bit

1...20 

1...20 s

Function code 05 - Write single coil

Register

Parameter description

Data Type

Value

Range

0x0001

Zero point calibration

Bit 0

0...1

On - Off 

WARRANTY POLICY

RECYCLING/DISPOSAL

The  parts  left  over  from  installation  should  be 
recycled  according  to  your  local  instructions. 
Decommissioned  devices  should  be  taken  to  a 
recycling site that specializes in electronic waste.

Function code 03 - Read input holding register

Register

Parameter description

Data Type

Value

Range

4x0001

Manufacturer

16 bit 

0...7

0...7

4x0002

Formula unit (Manufacturer=7)

16 bit

0...5

0: m3/s, 1: m3/h, 2: cfm, 3: l/s, 

4: m/s, 5: f/min

4x0003

K-factor integer

16 bit

0...9999

0...9999

4x0004

K-factor decimal

16 bit

0...999 

0...999

4x0005

Response time

16 bit

1...20 

1...20 s

-40C model: operation in cold environment

The lid of the device has to be closed when the operation temperature
is below 0 °C. The display needs 15 minutes to warm up if the device
is started in temperature below 0 °C.

NOTE! The power consumption rises and there can be an additional
error of 0,015 volts when the operation temperature is below 0 °C.

Содержание DPT-MOD Series

Страница 1: ... monitoring across centrifugal fans and blowers in duct air flow or pressure monitoring measuring air flow or pressure in VAV applications SPECIFICATIONS Performance Accuracy at applied pressure Model 2500 Pressure 125 Pa 1 2 Pa Pressure 125 Pa 1 1 Pa Model 7000 Pressure 125 Pa 1 5 2 Pa Pressure 125 Pa 1 5 1 Pa Accuracy specifications include general accuracy linearity hysteresis long term stabili...

Страница 2: ...YES NO NO INSTALLATION 1 Mount the device in the desired location see step 1 2 Open the lid and route the cable through the strain relief and connect the wires to the terminal block s see step 2 3 The device is now ready for configuration WARNING Apply power only after the device is properly wired STEP 2 WIRING DIAGRAMS For CE compliance a properly grounded shielding cable is required 1 Unscrew th...

Страница 3: ...rom common probe manufacturer s specifications Available K value range 0 001 9999 000 K VALUE 9000 000 SELECT UP DOWN 8 Select the address for Modbus 1 247 9 Select the baud rate 9600 19200 38400 ADDRESS 99 SELECT UP DOWN BAUD RATE 9600 SELECT UP DOWN 10 Select the parity bit None Even Odd PARITY BIT NONE SELECT UP DOWN STEP 4 ZEROING THE DEVICE NOTE Always zero the device before use To zero the d...

Страница 4: ...ith the autozero calibration are virtually maintenance free 3 Via Modbus register Make sure there is no pressure in the duct when the zeroing is done via Modbus register turns on and the display reads zeroing display option only see Figure 6 c The zeroing of the device will proceed automatically Zeroing is complete when the LED turns off and the display reads 0 display option only d Reinstall the p...

Отзывы: