HK Instruments DPT-MOD Series Скачать руководство пользователя страница 1

Copyright HK Instruments 2020

www.hkinstruments.fi

Installation version 7.0 2020

INSTALLATION

INSTRUCTIONS

DIFFERENTIAL PRESSURE TRANSMITTERS 

DPT-MOD Series

•  READ THESE INSTRUCTIONS CAREFULLY BEFORE 

ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS 
DEVICE.

•  Failure to observe safety information and comply with 

instructions can result in PERSONAL INJURY, DEATH AND/OR 

PROPERTY DAMAGE.

•  To avoid electrical shock or damage to equipment, disconnect 

power before installing or servicing and use only wiring with 
insulation rated for full device operating voltage.

•  To avoid potential fire and/or explosion do not use in potentially 

flammable or explosive atmospheres.

•  Retain these instructions for future reference.
•  This product, when installed, will be part of an engineered 

system whose specifications and performance characteristics 
are not designed or controlled by HK Instruments. Review 
applications and national and local codes to assure that the 
installation will be functional and safe. Use only experienced and 
knowledgeable technicians to install this device.

Thank you for choosing an HK Instruments DPT-MOD series differ-
ential pressure transmitter. The DPT-MOD series is intended for use 
in commercial environments. DPT-MOD is a multifunctional trans-
mitter for measuring volume flow, velocity, and static and differen-
tial pressure. The measurements can be read and the configuration 
done  via  Modbus  communication.  DPT-MOD  requires  less  wiring 
than  the  traditional  3-wire  transmitters  because  multiple  devices 
can be connected on serial line. DPT-MOD can also be used with 
several  different  measurement  probes  such  as  FloXact™  or  pitot 
tube, and air dampers.

The  DPT-MOD  series  is  comprised  of  DPT-MOD-2500  and  DPT-
MOD-7000  with  measurement  ranges  of  -250...2500  Pa  and 
-250...7000 Pa respectively. All models come with display and op-
tional autozero calibration.

DPT-MOD series devices are commonly used in HVAC/R systems for:

• fan, blower and filter monitoring
• pressure and flow monitoring
• valve and damper control
• pressure monitoring in cleanrooms
• air flow monitoring across centrifugal fans and blowers
• in-duct air flow or pressure monitoring
• measuring air flow or pressure in VAV applications

SPECIFICATIONS

Performance

Accuracy (at applied pressure):

Model 2500:

     Pressure < 125 Pa = 1 % + ±2 Pa

     Pressure > 125 Pa = 1 % + ±1 Pa

Model 7000:

     Pressure < 125 Pa = 1.5 % + ±2 Pa

     Pressure > 125 Pa = 1.5 % + ±1 Pa

(Accuracy specifications include: general accuracy, 

linearity, hysteresis, long term

stability, and repetition error)

Overpressure:

Proof pressure: 25 kPa

Burst pressure: 30 kPa

Zero point calibration:

Automatic autozero, manual pushbutton or via Modbus 

register

Response time:

1.0−20 s, selectable via menu or via Modbus register

Communication

Protocol: MODBUS over Serial Line

Transmission Mode: RTU

Interface: RS485

Byte format (11 bits) in RTU mode:

 

Coding System: 8-bit binary

 

Bits per Byte:

 

 

1 start bit

 

 

8 data bits, least significant bit sent  

 

 

first

 

 

1 bit for parity

 

 

1 stop bit

Baud rate: selectable in configuration

Modbus address: 1−247 addresses selectable in

configuration menu 

Technical Specifications

Media compatibility:

Dry air or non-aggressive gases

Pressure units (select via menu):

Pa, kPa, mbar, inWC, mmWC

Flow units (select via menu):

Volume: m

3

/s, m

3

/hr, cfm, l/s

Velocity: m/s, ft/min 

Measuring element:

MEMS, no flow-through

Environment:

Operating temperature: -20...50 °C,

-40C models: -40...50°C

Models with autozero calibration: -5...50 °C

Temperature compensated range  0...50 °C

Storage temperature: -40...70 °C

Humidity: 0 to 95 % rH, non condensing

Physical

Dimensions: 

Case: 90.0 x 95.0 x 36.0 mm

Weight: 

150 g

Mounting:

2 each 4.3 mm screw holes, one slotted

Materials:

Case: ABS

Lid: PC

Duct connectors: ABS

Tubing: PVC

Protection standard:

IP54 

Display

2-line display (12 characters/line)

 

Line 1: Volume or velocity measurement

 

Line 2: Pressure measurement

Size: 46.0 x 14.5 mm

Electrical connections:

4-screw terminal block

Wire: 0.2–1.5 mm

2

 (12–24 AWG)

Cable entry:

Strain relief: M16

Knockout : 16 mm

Pressure fittings

Male ø 5.0 mm and 6.3 mm

Electrical

Supply voltage: 

24 VAC or VDC ± 10 %

Power consumption:

< 1.3 W

Output signal:

via Modbus

Conformance

Meets requirements for CE marking:

EMC Directive 2014/30/EU

RoHS Directive 2011/65/EU

WEEE Directive 2012/19/EU

APPLICATIONS

INTRODUCTION

WARNING

COMPANY WITH

MANAGEMENT SYSTEM

CERTIFIED BY DNV GL

= ISO 9001 = ISO 14001 =

RoHS 2

2011/65/EU

Содержание DPT-MOD Series

Страница 1: ... monitoring across centrifugal fans and blowers in duct air flow or pressure monitoring measuring air flow or pressure in VAV applications SPECIFICATIONS Performance Accuracy at applied pressure Model 2500 Pressure 125 Pa 1 2 Pa Pressure 125 Pa 1 1 Pa Model 7000 Pressure 125 Pa 1 5 2 Pa Pressure 125 Pa 1 5 1 Pa Accuracy specifications include general accuracy linearity hysteresis long term stabili...

Страница 2: ...YES NO NO INSTALLATION 1 Mount the device in the desired location see step 1 2 Open the lid and route the cable through the strain relief and connect the wires to the terminal block s see step 2 3 The device is now ready for configuration WARNING Apply power only after the device is properly wired STEP 2 WIRING DIAGRAMS For CE compliance a properly grounded shielding cable is required 1 Unscrew th...

Страница 3: ...rom common probe manufacturer s specifications Available K value range 0 001 9999 000 K VALUE 9000 000 SELECT UP DOWN 8 Select the address for Modbus 1 247 9 Select the baud rate 9600 19200 38400 ADDRESS 99 SELECT UP DOWN BAUD RATE 9600 SELECT UP DOWN 10 Select the parity bit None Even Odd PARITY BIT NONE SELECT UP DOWN STEP 4 ZEROING THE DEVICE NOTE Always zero the device before use To zero the d...

Страница 4: ...ith the autozero calibration are virtually maintenance free 3 Via Modbus register Make sure there is no pressure in the duct when the zeroing is done via Modbus register turns on and the display reads zeroing display option only see Figure 6 c The zeroing of the device will proceed automatically Zeroing is complete when the LED turns off and the display reads 0 display option only d Reinstall the p...

Отзывы: