INSTALLATION

INSTRUCTIONS

DIFFERENTIAL PRESSURE TRANSMITTERS 

DPT-IO-MOD Series

•  READ THESE INSTRUCTIONS CAREFULLY BEFORE 

ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS 
DEVICE.

•  Failure to observe safety information and comply with 

instructions can result in PERSONAL INJURY, DEATH AND/OR 

PROPERTY DAMAGE.

•  To avoid electrical shock or damage to equipment, disconnect 

power before installing or servicing and use only wiring with 
insulation rated for full device operating voltage.

•  To avoid potential fire and/or explosion do not use in potentially 

flammable or explosive atmospheres.

•  Retain these instructions for future reference.
•  This product, when installed, will be part of an engineered 

system whose specifications and performance characteristics 
are not designed or controlled by HK Instruments. Review 
applications and national and local codes to assure that the 
installation will be functional and safe. Use only experienced and 
knowledgeable technicians to install this device.

SPECIFICATIONS

Thank you for choosing an HK Instruments DPT-IO-MOD series dif-
ferential pressure transmitter. The DPT-IO-MOD differential pres-
sure transmitter for air conforms to Modbus over serial line protocol, 
using RTU transmission mode and RS485 interface. The digital out-
put signal is sent over Modbus enabling the DPT-IO-MOD to con-
nect directly to a field communications network.

DPT-IO-MOD requires less wiring than traditional 3-wire transmit-
ters, since multiple devices can be connected on serial line.

The DPT-IO-MOD includes an Input terminal that enables reading 
of multiple other signals such as temperature or control relays over 
Modbus. The Input terminal has two input channels designed to ac-
cept 0−10 V, NTC10k, Pt1000, Ni1000/(-LG), and BIN IN (potential 
free  contact)  signals.  For  example,  DPT-IO-MOD  can  read  values 
from one differential pressure measurement point and two tempera-
ture measurement points. 

DPT-IO-MOD series devices are commonly used in HVAC/R

systems for:

•  fan, blower and filter monitoring
•  pressure and flow monitoring
•  valve and damper control
•  pressure monitoring in cleanrooms

SPECIFICATIONS

Performance

Accuracy (from applied pressure):

Model 2500:

     Pressure < 125 Pa = 1 % + ±2 Pa

     Pressure > 125 Pa = 1 % + ±1 Pa

Model 7000:

     Pressure < 125 Pa = 1.5 % + ±2 Pa

     Pressure > 125 Pa = 1.5 % + ±1 Pa    

 

(Including: general accuracy, linearity, hysteresis, long 

term stability and repetition error)

Input accuracy:

 

<0,5%

Response time:

1...20 s selectable via menu

Overpressure:

Proof pressure: 25 kPa

Burst pressure: 30 kPa

Communication

Protocol: MODBUS over Serial Line

Transmission Mode: RTU

Interface: RS485

Byte format (11 bits) in RTU mode:

 

Coding System: 8-bit binary

 

Bits per Byte:

 

 

1 start bit

 

 

8 data bits, least significant bit sent  

 

 

first

 

 

1 bit for parity

 

 

1 stop bit

Baud rate: selectable in configuration

Modbus address: 1−247 addresses selectable in

configuration menu

Zero point calibration options:

• Manual pushbutton autozero

• Via Modbus write coil

Technical Specifications

Media compatibility:

Dry air or non-aggressive gases

Measuring units:

Selectable via menu (Pa, mbar, inchWC, mmWC, psi)

Measuring element:

MEMS, no flow-through

Environment:

Operating temperature: -20...+50 °C

Temperature compensated range 0...+50 °C

Storage temperature: -40...+70 °C

Humidity: 0 to 95 % rH

Physical

Dimensions: 

Case: 102.0 x 71.5 x 36.0 mm 

Weight: 

150 g, with accessories 290 g

Mounting: 

2 each 4.3 mm screw holes, one slotted

Materials:   

Case: ABS

Lid: PC 

Pressure inlets: Brass

Duct connectors: ABS

Tubing: PVC

Protection standard: 

IP54

Display:

2-line display (12 characters/line)

Line 1: active measurement

Line 2: units

Electrical Connections:

4+3 spring load terminals, max 1.5 mm

2

Cable Entry: M20

Pressure fittings:

Male ø 5,0 mm and 6,3 mm

Electrical

Supply voltage: 

24 VAC or VDC ± 10 %

Power consumption:

< 1.3 W

Output signal:

via Modbus

Input signals:

2 x input (0...10v, NTC10k, Pt1000, NI1000/(-LG), or 

BIN IN)

 

Conformance

Meets requirements for CE marking:

EMC directive 2014/30/EU

RoHS Directive 2011/65/EU

WEEE Directive 2012/19/EU

INTRODUCTION

APPLICATIONS

WARNING

COMPANY WITH

MANAGEMENT SYSTEM

CERTIFIED BY DNV GL

= ISO 9001 = ISO 14001 =

RoHS 2

2011/65/EU

Содержание DPT-IO-MOD Series

Страница 1: ...asurement points DPT IO MOD series devices are commonly used in HVAC R systems for fan blower and filter monitoring pressure and flow monitoring valve and damper control pressure monitoring in cleanrooms SPECIFICATIONS Performance Accuracy from applied pressure Model 2500 Pressure 125 Pa 1 2 Pa Pressure 125 Pa 1 1 Pa Model 7000 Pressure 125 Pa 1 5 2 Pa Pressure 125 Pa 1 5 1 Pa Including general ac...

Страница 2: ...y for configuration WARNING Apply power only after the device is properly wired 1 Select the mounting location duct wall panel 2 Use the device as a template and mark the screw holes 3 Mount with appropriate screws Figure 1b Mounting orientation Figure 1c Application connections DPT DPT Display connection A B 24 V GND LEDs Joystick 1 Joystick 2 Joystick 3 Select Up Down Menu buttons Terminal block...

Страница 3: ...er 3x0008 1 Activate the device Menu by pushing the the select button for 2 seconds 2 Select the address for Modbus 1 247 BAUD RATE 9600 SELECT UP DOWN ADDRESS 99 SELECT UP DOWN PARITY BIT NONE SELECT UP DOWN 3 Select the baud rate 9600 19200 38400 4 Select the parity bit None Even Odd 5 Select the pressure unit for display Pa inchWC mmWC psi mbar PRESS UNIT Pa SELECT UP DOWN 6 Select the response...

Страница 4: ...y for goods that have been replaced or repaired within the warranty however only to the expiration of the original product s warranty time The warranty includes the repair of a defective part or device or if needed a new part or device but not installation or ex change costs Under no circumstance is the seller liable for damages compensation for indirect damage Register Parameter description Data ...

Отзывы: