background image

Copyright HK Instruments 2021

www.hkinstruments.fi

Installation version 7.0 2021

The  seller  is  obligated  to  provide  a  warranty  of  five  years  for  the  delivered 
goods regarding material and manufacturing. The warranty period is consid-
ered to start on the delivery date of the product. If a defect in raw materials or a 
production flaw is found, the seller is obligated, when the product is sent to the 
seller without delay or before expiration of the warranty, to amend the mistake 
at his/her discretion either by repairing the defective product or by delivering 
free of charge to the buyer a new flawless product and sending it to the buyer. 
Delivery costs for the repair under warranty will be paid by the buyer and the 
return costs by the seller. The warranty does not comprise damages caused by 
accident, lightning, flood or other natural phenomenon, normal wear and tear, 
improper or careless handling, abnormal use, overloading, improper storage, 
incorrect care or reconstruction, or changes and installation work not done by 
the seller or his/her authorized representative. The selection of materials for 
devices prone to corrosion is the buyer’s responsibility, unless otherwise is le-
gally agreed upon. Should the manufacturer alter the structure of the device, 
the seller is not obligated to make comparable changes to devices already pur-
chased. Appealing for warranty requires that the buyer has correctly fulfilled 
his/her duties arisen from the delivery and stated in the contract. The seller 
will give a new warranty for goods that have been replaced or repaired within 
the  warranty,  however  only  to  the  expiration  of  the  original  product’s  war-
ranty time. The warranty includes the repair of a defective part or device, or if 
needed, a new part or device, but not installation or exchange costs. Under no 
circumstance is the seller liable for damages compensation for indirect damage.

Register

Parameter description

Data Type

Value

Range

4x0001

Parameter for P-controller

16 bit

0...3

0=CO2, 1=rH, 2=TE, 3=MAX

4x0002

CO2 hIgh limit

16 bit

500...2000

500...2000 ppm

4x0003

CO2 low limit

16 bit

0...1900

0...1900 ppm

4x0004

rH high limit

16 bit

100...1000

10.0...100.0 %

4x0005

rH low limit

16 bit

0...900

0.0...90.0 %

4x0006

TE high limit

16 bit

50...500

5.0...50.0 °C

4x0007

TE low limit

16 bit

0...450

0...45.0 °C

4x0008

Parameter for relay

16 bit

0...3

0=CO2, 1=rH, 2=TE, (3=Off)

4x0009

CO2 relay on

16 bit

500...1950

500...1950 ppm

4x0010

CO2 relay off

16 bit

450...1900

450...1900 ppm

4x0011

rH relay on

16 bit

15...990

1.5...99.0 %

4x0012

rH relay off

16 bit

10...985

1.0...98.5 %

4x0013

TE relay on

16 bit

15...490

1.5...49.0 °C

4x0014

TE relay off

16 bit

10...485

1.0...48.5 °C

Function code 03 - Read input holding register

Function code 04 - Read input register

Register

Parameter description

Data Type

Value

Range

3x0001

Parameter for P-controller

16 bit 

0...3

0=CO2, 1=rH, 2=TE, 3=MAX

3x0002

CO2 reading

16 bit

0...2000

0...2000 ppm

3x0003

rH reading

16 bit

0...1000

0,0...100.0 %

3x0004

Temp. reading

16 bit

0...500

0.0...50.0 °C

3x0005

CO2 high limit

16 bit

500...2000

500...2000 ppm

3x0006

CO2 low limit

16 bit

0...1900

0...1900 ppm

3x0007

rH high limit

16 bit

100...1000

10.0...100.0 %

3x0008

rH low limit

16 bit

0...900

0.0...90.0 %

3x0009

TE high limit

16 bit

50...500

5.0...50.0 °C

3x0010

TE low limit

16 bit

0...450

0...45.0 °C

3x0011

Parameter for relay

16 bit

0...3

0=CO2, 1=rH, 2=TE, (3=Off) 

3x0012

CO2 relay on

16 bit

500...1950

500...1950 ppm

3x0013

CO2 relay off

16 bit

450...1900

450...1900 ppm

3x0014

rH relay on

16 bit

15...990

1.5...99.0 %

3x0015

rH relay off

16 bit

10...985

1.0...98,5 %

3x0016

TE relay on

16 bit

15...490

1.5...49.0 °C

3x0017

TE relay off

16 bit

10...485

1.0...48.5 °C

MODBUS REGISTERS 

CONTINUED

Function code 16 - Write multiple registers

Register

Parameter description

Data Type

Value

Range

4x0001

Parameter for P-controller

16 bit 

0...3

0=CO2, 1=rH, 2=TE, 3=MAX

4x0002

CO2 hIgh limit

16 bit

500...2000

500...2000 ppm

4x0003

CO2 low limit

16 bit

0...1900

0...1900 ppm

4x0004

rH high limit

16 bit

100...1000

10.0...100.0 %

4x0005

rH low limit

16 bit

0...900

0.0...90.0 %

4x0006

TE high limit

16 bit

50...500

5.0...50.0 °C

4x0007

TE low limit

16 bit

0...450

0...45.0 °C

4x0008

Parameter for relay

16 bit

0...3

0=CO2, 1=rH, 2=TE, (3=Off)

4x0009

CO2 relay on

16 bit

500...1950

500...1950 ppm

4x0010

CO2 relay off

16 bit

450...1900

450...1900 ppm

4x0011

rH relay on

16 bit

15...990

1.5...99.0 %

4x0012

rH relay off

16 bit

10...985

1.0...98.5 %

4x0013

TE relay on

16 bit

15...490

1.5...49.0 °C

4x0014

TE relay off

16 bit

10...485

1.0...48.5 °C

RECYCLING/DISPOSAL

The  parts  left  over  from  installation  should  be 
recycled  according  to  your  local  instructions. 
Decommissioned  devices  should  be  taken  to  a 
recycling site that specializes in electronic waste.

WARRANTY POLICY

Register

Parameter description

Data Type

Value

Range

1x0001

Relay status

Bit 0

0...1

0=Off - 1=On

1x0002

Relay trend

Bit 0

0...1

0=Increasing, 1=Decreasing

1x0003

Timer status

Bit 0

0...1

0=Off - 1=On

Function code 02 - Read input status

Function code 06 - Write single register

Register

Parameter description

Data Type

Value

Range

4x0001

Parameter for P-controller

16 bit 

0...3

0=CO2, 1=rH, 2=TE, 3=MAX

4x0002

CO2 hIgh limit

16 bit

500...2000

500...2000 ppm

4x0003

CO2 low limit

16 bit

0...1900

0...1900 ppm

4x0004

rH high limit

16 bit

100...1000

10.0...100.0 %

4x0005

rH low limit

16 bit

0...900

0.0...90.0 %

4x0006

TE high limit

16 bit

50...500

5.0...50.0 °C

4x0007

TE low limit

16 bit

0...450

0...45.0 °C

4x0008

Parameter for relay

16 bit

0...3

0=CO2, 1=rH, 2=TE, (3=Off)

4x0009

CO2 relay on

16 bit

500...1950

500...1950 ppm

4x0010

CO2 relay off

16 bit

450...1900

450...1900 ppm

4x0011

rH relay on

16 bit

15...990

1.5...99.0 %

4x0012

rH relay off

16 bit

10...985

1.0...98.5 %

4x0013

TE relay on

16 bit

15...490

1.5...49.0 °C

4x0014

TE relay off

16 bit

10...485

1.0...48.5 °C

STEP 5: MODBUS REGISTERS

Functions for Modbus communication:

Function Code

Description

01

Read coil status

02

Read input status

03

Read holding registers

04

Read input registers

05

Force single coil

06

Preset single register

07

Read exception status

15

Force multiple coils

16

Preset multiple registers

17

Report slave ID

Jumper settings 

CONTINUED

Function code 05 - Write single coil

Register

Parameter description

Data Type

Value

Range

0x0001

Relay trend

Bit 0

0...1

0=Increasing, 1=Decreasing

Jumper installed to the left side pins:

0–10 V output selected

N/A
N/A
Analog

0...10 V   4...20 mA

Jumper installed to the right side pins:

4–20 mA output selected

N/A
N/A
Analog

0...10 V   4...20 mA

Figure 4

2) Locking the display:

Install the jumper to lock the display to prevent access to the 
configuration menu after installation is completed (see the 
schematics for the location of the pins).

Содержание CDT-MOD-2000 Series

Страница 1: ...where there is a constant source of carbon dioxide present for example hospitals and greenhouses SPECIFICATIONS Performance Measurement ranges CO2 400 2000 ppm Temperature 0 50 C Relative humidity 0 100 Accuracy CO2 40 ppm 2 of reading DC model 75 ppm or 10 of reading whichever is greater Temperature 0 5 ºC Relative humidity 2 3 at 0 50 C and 10 90 rH Total error band includes accuracy hysteresis ...

Страница 2: ...a with good ventilation and an average temperature where it will be responsive to changes to the room conditions The CDT MOD should be mounted on a flat surface Do not locate the CDT MOD where it can be affected by Direct sunlight Drafts or dead areas behind doors Radiant heat from appliances Concealed pipes or chimneys Outside walls or unheated uncooled areas 2 Use the device as a template and ma...

Страница 3: ...put 0 2 10 V 4 20 mA output Figure 2b Wiring diagram Power input signal output Wires can be routed through the square opening in the back plate Wires can be routed through the top knockouts Wires can be routed through the bottom knockouts Figure 2d Wiring diagram Relay NC COM NO STEP 2 WIRING DIAGRAMS NOTE When using long connection wires it may be necessary to use a separate GND wire for voltage ...

Страница 4: ...0 0 90 0 3x0009 TE high limit 16 bit 50 500 5 0 50 0 C 3x0010 TE low limit 16 bit 0 450 0 45 0 C 3x0011 Parameter for relay 16 bit 0 3 0 CO2 1 rH 2 TE 3 Off 3x0012 CO2 relay on 16 bit 500 1950 500 1950 ppm 3x0013 CO2 relay off 16 bit 450 1900 450 1900 ppm 3x0014 rH relay on 16 bit 15 990 1 5 99 0 3x0015 rH relay off 16 bit 10 985 1 0 98 5 3x0016 TE relay on 16 bit 15 490 1 5 49 0 C 3x0017 TE relay...

Отзывы: