HTM(HPV)-20N Series
HITROL CO., LTD.
11
Activation Point Setting
Set the current state as the detection point. (
※
However, the medium must come in
contact with the sensor.)
Activation Point Adjustment
Detection point is customizable according to the specific gravity of the medium and the area
that comes in contact with the sensor. ( - Adjust insensitively, - Adjust sensitively)
Relay Delay Time Adjustment
Delay time can be set for the relay operation after the sensor detects the medium.
Relay Out Control
You can change the state of the output contact. (N.C.
N.O.
…
N.C.)
Press and hold the
+
buttons for 1 second to turn on and off the green
LED and thus finish the setting.
Press and hold the
+
buttons to turn on the red LED.
Use
or
to set the Delay Time with the buton. Then, press and hold the
+
buttons for 1 second to turn on and off the green LED and thus finish
the setting (max. of 60 sec. / min. of 1 sec. @ 1 sec. step).
Press and hold the button to turn on the red LED.
Use
or
to set the detection point with the
button. Then, press and
hold the button for 1 second.
Press
and then press and hold the
button for 1 second to turn on and off
the green LED and thus finish the setting.