If fields X.7 and X.3 have been filled out with digit 1, both relays (4 and 5) are inactive. 
Original configuration of code K45 is set as 0010 0010. 
 
 

7.

 

Short operation manual. 

 

After  power  supply  has  been  switched  on info  about the  company  is  displayed,  followed  by 

the test of the system (after 2 sec.). If no problems are detected the password will be verified. Every 
RTT has its own separate password consisting of 4 digits. 
 
The built-in display has 4 lines, 20 digits each. 
When the device is working normally, abbreviated information about its operation is being displayed. 
Sensor and relay numbers are displayed in the first line. 
Information about the condition of the relay and sensor is shown in an abbreviated form in the second 
line. 
Explanation of the abbreviations used are displayed after entering the key No. 8. 
 
ERR –missing  data or error 
ZER – sensor has been torn out 
ZW – sensor is short connected 
WŁ – relay is on 
WYŁ – relay is off 
TW – time relay is on 
TWY – time relay is off 
MWŁ – maximum temperature control mode is on 
MWY - maximum temperature control mode is off 
MER - maximum temperature control mode is malfunctioning 
3WŁ – time relay 3 is on 
3WY – time relay 3 is off 
2WŁ – parallel mode is on 
2WY – parallel mode is off 
 
Explanation of the abbreviations not displayed: 
 
TxL – threshold temperature when relay is on 
TxH - threshold temperature when relay is off 
 
For relays 4 and 5 following abbreviations are used: 
 
T4L – determined delay for time relay (in sec.) 
T5L – determined time relay (in min.) 
 
In  the  third  line  current  temperature  or  time  (given  in  sec.  or  min.)  is  displayed.  If  any  faults  occur 
three strokes will be displayed instead of the temperature. 
 
Current time and date is displayed in the fourth line. 
 
 
After pressing any key MENU is activated. It allows for: 
 
1.

 

Setting the clock 
a) press 1 
b) when appears menu with on figure blinking grid (1) press (E) to setup a new time and dates or 
(P) return to main purpose menu.. 

 
Exemplary appearance of display with main menu. 

Содержание RTT8

Страница 1: ...HiTiNSp z o o 40 432 Katowice ul Szopienicka 62 C Tel fax 48 32 353 41 31 48 32 601 20 60 www hitin pl Temperature control relay RTT8 DTR Katowice 2003r V27 04 2012...

Страница 2: ...C Maximum switch power 2kVA 192W Maximum switch voltage 400V AC 150V DC Operation in environment free from any inflammable or chemically active dusts and gases is essential 4 Installation Fasten the d...

Страница 3: ...ll be switched on after a desired period The previously set time interval is counted down after the testing procedures initialised when power is on have been completed Relay 5 Functioning of the relay...

Страница 4: ...sensor is short connected W relay is on WY relay is off TW time relay is on TWY time relay is off MW maximum temperature control mode is on MWY maximum temperature control mode is off MER maximum tem...

Страница 5: ...new data When you finish inscribing a new data and code will appear question about registration a new data to memory When you press E data will be save and return to main menu When you press P you re...

Страница 6: ...green lamp normal operation yellow lamp indicates data transfer to an outside computer red lamp error Dwg 1 Arrangement of basic elements on the pcb...

Страница 7: ...Dwg 2 Housing dimensions 7 0 1 2 0 1 8 4 6 0 2 1 2 2 1 6 11...

Страница 8: ...Dwg 3 Typical RTT8 connection by Pt100 sensors...

Страница 9: ...Dwg 4 Position of the mounting holes 197 139 5...