hitin RTT8 Скачать руководство пользователя страница 2

1.  Introduction 

 

Electronic  device  RTT  8  is  meant  to  find  out  excess  temperature  of  transformers  equipped 

with  PT100 sensors. 

 
 

2.

 

Use 

 

RTT 8 is dedicated to monitor temperature of both dry and resinblock transformers equipped 

with  PT100  sensors.  It  is  able  to  control  temperature  of  up  to  5  sensors.  The  relay  with  switching 
contacts is applied as the device outputs for each temperature threshold. 
 
 

3.

 

Technical data 

Nominal Voltage: 

 

 

42 – 240 V AC or 42 – 240 V DC without switchings 

Maximum absorbed power: 

 

10VA 

Number of inputs 

 

 

5 sensors PT100 

Isolation: 
Power supply to housing 

 

2,5 kV 

Inputs to housing 

 

 

2,5 kV 

Output to housing 

 

 

2,5 kV 

Power supply to output   

 

2,5 kV 

Power supply to input   

 

2,5 kV 

Input to output   

 

 

2,5 kV 

Protection 

 

 

 

IP 65 

Dimensions 

 

 

 

212x216x120 (see dwg.2) 

Position of operation 

 

 

any 

Weight  

 

 

 

1,5 kg 

Temperature scale 

 

 

70°C – 220°C with 1°C resolution 

Time relay delay 

 

 

70s – 220s or 70min. – 220 min.  

Operating temperature   

 

0 – 45°C 

Storage temperature 

 

 

-25C – 85C 

Diameter of linking cables 

 

max 2,5 mm

Maximum switch current: 

 

8A / 250VAC/24VDC 

Maximum switch power: 

 

2kVA / 192W 

Maximum switch voltage: 

 

400V AC / 150V DC 

Operation in environment free from any inflammable or chemically active dusts and gases is essential. 
 
 

4.

 

Installation 

 

Fasten the device with three M5 screws through the holes in the bottom part of the housing. 

RTT8  ought  to  be  used  and  kept  away  from  water,  conducting  or  not  conducting  dusts,  explosive, 
inflammable and chemically active gases, dusts and vapours. Connect protective earth, power supply, 
and the sensors. Connect output contacts as desired. Connect data transfer cables (option). 

 
 
5.

 

Functioning of the operating programme 

 

After  switching  on  power  supply  initiation  of  the  display  is  carried  out.  Then  the  internal 

system is tested. At the next step the programme is proceeding to verification of the user’s password.  
If  the  password  is  entered,  no  changes  to  the  original  settings

 

will  be  possible.  After  30  days  of 

operation all functions of the device will be blocked unless the password is re-entered.  
If the password is not entered the programme will start to work with original settings after it has been 
switch on for the first time. 
 

If any faults occur (i.e. heavy interference or lack of power supply) the device can return to its 

initial settings. 

Содержание RTT8

Страница 1: ...HiTiNSp z o o 40 432 Katowice ul Szopienicka 62 C Tel fax 48 32 353 41 31 48 32 601 20 60 www hitin pl Temperature control relay RTT8 DTR Katowice 2003r V27 04 2012...

Страница 2: ...C Maximum switch power 2kVA 192W Maximum switch voltage 400V AC 150V DC Operation in environment free from any inflammable or chemically active dusts and gases is essential 4 Installation Fasten the d...

Страница 3: ...ll be switched on after a desired period The previously set time interval is counted down after the testing procedures initialised when power is on have been completed Relay 5 Functioning of the relay...

Страница 4: ...sensor is short connected W relay is on WY relay is off TW time relay is on TWY time relay is off MW maximum temperature control mode is on MWY maximum temperature control mode is off MER maximum tem...

Страница 5: ...new data When you finish inscribing a new data and code will appear question about registration a new data to memory When you press E data will be save and return to main menu When you press P you re...

Страница 6: ...green lamp normal operation yellow lamp indicates data transfer to an outside computer red lamp error Dwg 1 Arrangement of basic elements on the pcb...

Страница 7: ...Dwg 2 Housing dimensions 7 0 1 2 0 1 8 4 6 0 2 1 2 2 1 6 11...

Страница 8: ...Dwg 3 Typical RTT8 connection by Pt100 sensors...

Страница 9: ...Dwg 4 Position of the mounting holes 197 139 5...

Отзывы: