![Hitecsa Verne WPHA HE 091 Скачать руководство пользователя страница 35](http://html1.mh-extra.com/html/hitecsa/verne-wpha-he-091/verne-wpha-he-091_installation-operation-and-maintenance-manual_2140043035.webp)
35
IOM_WPHBA HE-WPHA HE_091a1201_207815_180701_EN
HORIZONTAL WATER-AIR COMPACT PACKAGED UNITS
WPHA HE / WPHBA HE
MAINTENANCE
FAN WITH EC MOTOR
Diagnosis / Failures
Status LED, Diagnostics through flash code
LED Code
Relay contacts 11-14
Fan alarms
Causes (Explanation)
OFF
OPEN
Power supply shut-off
ON
CLOSED
Correct operation without failures
1x
CLOSED
No release = OFF
2x
CLOSED
Temperature management activated
3x
OPEN
HALL-IC failure
4x
OPEN
Phase failure (only with type 3 ~)
5x
OPEN
Motor blocked
6x
OPEN
IGBT failure
7x
OPEN
Overvoltage of the intermediate circuit
8x
OPEN
Overvoltage of the intermediate circuit
9x
CLOSED
IGBT cooling pause
11x
OPEN
Motor start failure
12x
OPEN
Network voltage too low
13x
OPEN
Network voltage too high
14x
OPEN
Peak current failure
17x
OPEN
Temperature alarm