13
IOM_WPHBA HE-WPHA HE_091a1201_207815_180701_EN
HORIZONTAL WATER-AIR COMPACT PACKAGED UNITS
WPHA HE / WPHBA HE
TECHNICAL SPECIFICATIONS
VERNE HE SERIE
701
751
1001
1201
REFRIGERANT
Type
R-410A
Global warming potential (GWP) (5)
2088
Refrigerant load WPHA
kg
1.6
1.7
2.4
3
Refrigerant load WPHBA
kg
4
4.2
6.1
6.3
COMPRESSOR
Type
Scroll
Quantity
1
Voltage
V / ~ / Hz
400/3/50
Oil type
PVE
PVE
PVE
POE
Oil quantity in compressor
L
1.57
2.46
2.46
3.31
EVAPORATOR FAN
Type
Radial with EC motor
Quantity
1
Size
mm
400
400
450
450
Nominal air flow
m
³/h
3400
4300
6200
7000
Static pressure available
Pa
50
62
75
75
Maximum pressure available
Pa
1100
975
580
400
Motor nominal Capacity
W
2.4
2.4
2.0
2.0
Nominal speed
r.p.m.
1242
1509
1476
1643
Power supply
V / ~ / Hz
400/3/50
INDOOR HEAT EXCHANGER
Type
Coil with aluminium fins and copper pipes
Frontal area
m
²
0.45
0.45
0.84
0.84
Fin spacing
mm - "
2.1 -
3/8”
OUTDOOR HEAT EXCHANGER
Type
Brazed plates
Quantity
1
Water connections (gas male screw)
"
1 ¼”
Number of plates
32
32
52
52
ELECTRICAL DATA
Voltage
V / ~ / Hz
400 / 3+N / 50
Maximum current input
A
17.89
19.64
23.01
26.12
Start-up current
A
90.79
128.74
128.51
150.42
DIMENSIONS AND WEIGHT
Length
mm
1385
1385
1930
1930
Width
mm
940
940
1040
1040
Height
mm
620
620
690
690
Conduit
mm x mm
450x500
450x500
550x550
550x550
Weight
kg
160
180
230
250
SOUND LEVEL
Sound pressure at 2 m
dB (A)
65
65
66
67
Total sound power (Lw)
dB (A)
81.5
82.0
82.5
83.5
5)
GWP:
Global warming potential (climatic) of 1 kg of greenhouse gas relative to 1 kg of CO2, calculated in terms
of 100-year warming potential.