DESCRIPTION OF THE MODBUS PARAMETERS
Proceed to enabling the communication with a PGD or a Mini PGD terminal so as to be able to change the MODBUS parameters from
the TH-TUNE terminal: Enable the supervisor in the factory level menu and enable Start / Stop of the unit through supervisor.
ADDRESS PARAMETER CONFIGURATION
Press the central button several times until
ADDR
appears
.
(Supervision is not activated if these
characters are not displayed).
Turn the central button to select the direction
(1-200).
Press the central button once to confirm.
BAUD (RATE) PARAMETER CONFIGURATION
Press the central button several times until
BAUD
appears
.
Turn the central button to select the speed.
(0, 1, 2, 3, 4)
0 → 1200
1 → 2400
2 → 4800
3 → 9600
4 → 19200
Press the central button once to confirm.