GENERAL OPERATING FEATURES: 

 

 

 

Digital electronic thermostat, large blue LCD display with adjustable backlighting 

 

Developed and designed to control fan coil and hydronic cassette units 

 

Hourly and weekly programming as standard 

 

Perennial calendar clock and integral battery as standard 

 

RS485 bus connection fitting as standard 

 

Device totally controlled using Modbus communications protocol 

 

Operation with 2 pipe 

− 4 pipe − fan only − heat pump (P04) systems 

 

Control of electric heater as alternative or addition (P07) 

 

Control of outdoor air recycling gate valve 

 

Control of humidification/dehumidification/read only with internal humidity sensor (optional) 

 

Automatic/manual/centralized setting of SUM/WlN operating mode switching (P09) 

 

Continual or 

thermostat−controlled fan operation (P05) 

 

Automatic/manual fan speed switching 

 

Air temperature monitored by internal probe or remote air probe (automatic probe recognition) 

 

Antifreeze function even with thermostat off 

 

Filter fouling alert as standard 

 

Fan trigger temperature thresholds can be set separately for heating and cooling operation (P18 and 
P19) 

 

SUM/WlN switching temperature thresholds can be set separately for heating and cooling operation 
(P16 and P17) 

 

Automatic SUM/WlN mode switch on the basis of output temperature (P08 and P09) 

 

Automatic SUM/WlN mode switch on the basis of air temperature (P09) 

 

Centralized comfort/economy operating control 

 

Control of 

ON−OFF valves, modulating valves and floating valves integrated in a single product code 

 

Control of conventional 

3−speed fan units and energy−saving brushless units 

 

lnputs for control of window contact, economy contact, auxiliary contact, and bathroom and fire alarm 

 

lnputs for hotel functions, such as: bathroom alarm 

− fire alarm − room empty/occupied 

 

Outputs for hotel functions, such as: courtesy light control 

− control of bathroom fan with room 

occupied 

 

lnfra−red remote control receiver (optional) 

 

Monitoring of fan power drawdown with control of failure thresholds and alarm output (P35 and P36) 

 

Setting/reduction of length of temperature scale controllable by parameters (P23 and P24) 

 

Keyboard lock function 

 

Diagnostic function for troubleshooting of thermostat and system malfunctions 

 

Quiet regulation thanks to use of triac control technology 

Содержание idigit control

Страница 1: ...USER MANUAL 07 16 207674 Rev100 iDigit CONTROL Digital thermostat for fan coil units...

Страница 2: ...nstallations Our approach is based in efficiency flexibility manageability and practical solutions It has built a hallmark of our product catalogue The versatility of our factories allows us to contri...

Страница 3: ...L Digital thermostat for fan coil units CONTENTS GENERAL OPERATING FEATURES 4 THERMOSTAT OPERATION 5 LEVEL PARAMETERS 11 ELECTRICAL CONNECTION DIAGRAM 12 POLE TERMINAL BOARD 14 ELECTRICAL CONNECTIONS...

Страница 4: ...hresholds can be set separately for heating and cooling operation P18 and P19 SUM WlN switching temperature thresholds can be set separately for heating and cooling operation P16 and P17 Automatic SUM...

Страница 5: ...t is pressed or hold down for 5 to decrease the setting at high speed After 10 the device automatically quits the temperature setpoint setting function to quit faster press the on off key for a short...

Страница 6: ...l selection mode is active or at the minimum speed if the current selection mode is automatic lf the system output probe is connected the fan operates on the following principle 2 pipe system the devi...

Страница 7: ...R glage de l heure et de la date de l horloge Press the menu key scroll through it with the key and select TIME with the menu key HRS the hour figures flash use the keys to set the current hours and c...

Страница 8: ...Press the menu key and set the starting hours for band F2 Press the menu key and set the starting minutes of band F2 Press the menu key and set the operating temperature for band F2 Use the key to sel...

Страница 9: ...L Digital thermostat for fan coil units Table 3 example of weekly time program set in table 2 The icon on the display illuminates to indicate that the thermostat is performing a daily program Day F1 T...

Страница 10: ...d level is protected by a password To access the first level parameter menu press the menu key use the key to scroll the menu and confirm the PAr option by pressing the menu key for 5 Parameter P01 wi...

Страница 11: ...rmostat 1 continuous P06 OUTPUT TYPE 0 ON OFF 0 ON OFF valves 1 wax solenoid valve with temperature algorithm 2 floating 2 pipes P07 ELECTRlC HEATER 0 none 0 none 1 replacement 2 additional 3 addition...

Страница 12: ...19 SUMMER FAN ON 15 0 C 5 0 25 0 C P20 ANTlFREEZE C 4 0 C 0 0 10 0 C P21 FLOATlNG ACTUATOR STROKE 150 0 400 P22 FlLTER FOULED 6 x 300h 0 20 x 300h P23 SETPOlNT BOTTOM LlMlT 10 0 C 10 0 30 0 C P24 SETP...

Страница 13: ...8 AlR SETPOlNT 20 0 C 10 30 C P39 MEASURlNG SCALE C F 0 C 0 C 1 F P40 BOX BACKLlGHT MlNlMUM LlGHT lN STANDBY MODE 0 off 0 5 P41 LCD BACKLlGHT MlNlMUM LlGHT lN STANDBY MODE 0 off 0 5 P42 MODBUS NETWORK...

Страница 14: ...max 1A 230Vac TK4 TK5 TK6 solenoid valve heater control triac max 0 1A 230Vac VF floating valve VF floating valve VC cooling valve VH heating valve heating and cooling for 2 pipe system R auxiliary o...

Страница 15: ...mostat for fan coil units ELECTRICAL CONNECTIONS TO RJ45 CONNECTOR Key CW window contact EC economy contact DMC cooling valve modulating output 0 10V DMH heating valve modulating output 0 10V CN1 auxi...

Страница 16: ...207674 Rev100 HIPLUS AIRE ACONDICIONADO S L Masia Torrents 2 Tel 34 93 893 49 12 Fax 34 93 893 96 15 08800 Vilanova i la Geltr Barcelona Spain www hitecsa com Rights reserved subject to change withou...

Отзывы: