iDigit CONTROL
Digital thermostat for fan coil units
Table 6: 2nd level parameters
Parameter
Function
Default setting
Possible settings
P33
AUXlLlARY DlGlTAL lNPUT
0 = fan TM thermostat
0 = fan TM thermostat
1 = bathroom alarm
2 = smoke alarm
P34
lNPUT CONFlGURATlON
0 = configuration 0
0 = configuration 0
1 = configuration 1
2 = configuration 2
3 = configuration 3
P35
MlNlMUM CURRENT THRESHOLD
0 = control function off
0….50 (mA x 10)
P36
MAXlMUM CURRENT THRESHOLD
0 = control function off
0….200 (mA x 10)
P37
SENSOR TYPE
0 = NTC 10K
0 = NTC 10K
1 = NTC 20K
P38
AlR SETPOlNT
20.0˚C
10….30˚C
P39
MEASURlNG SCALE ˚C/˚F
0 = ˚C
0 = ˚C
1 = ˚F
P40
BOX BACKLlGHT MlNlMUM LlGHT lN
STANDBY MODE
0 = off
0….5
P41
LCD BACKLlGHT MlNlMUM LlGHT lN
STANDBY MODE
0= off
0….5
P42
MODBUS NETWORK ADDRESS
1
0….255 (0 = broadcast)
P43
ON−OFF VALVE HYSTERESlS (%)
5%
2….100%
P44
VALVE OPENlNG TlME lN HP MODE
5’
1….100’
P45
VALVE OPENlNG PERlODlC CYCLE
lN HP MODE
60’
1….999’
P46
WlNTER SETPOlNT WlTH SETUP 3
(HOTEL MODE)
18.0˚C
5.0˚C….30˚C
P47
SUMMER SETPOlNT WlTH SETUP 3
(HOTEL MODE)
27.0˚C
5.0˚C….30˚C
P48
HUMlDlTY (RH) SETPOlNT
50
0….100%
P49
MODULATlNG VALVE
MlNlMUM LlMlT
0%
0.…50%
P50
MODULATlNG VALVE MAXlMUM
LlMlT
100%
50%....100%
P51
FAN MODULATlNG VALVE
MlNlMUM LlMlT
0%
0.…50%
P52
FAN MODULATlNG VALVE
MAXlMUM LlMlT
100%
50%....100%
P53
ENABLING FAN
SETTING SPEED MANUAL
1
0 = OFF
1 = ON