AIR COOLED WATER CHILLERS
– AXIAL FANS
EKWXA/EKWXBA
►
ALARMS
CODE
DESCRIPTION
TYPE OF REBOOT
COMPRESSOR
WATER
PUMP
EXTERNAL FAN
ANTI-FREEZE
HEATER
A03
Evaporator flow switch
Manual
OFF
OFF
OFF
OFF
A09
High temperature
Notification
-
-
-
-
A10
Evaporator pump service time limits
exceeded
Notification
-
-
-
-
A12
Condenser fan service time limits
exceeded
Notification
-
-
-
-
A51
Condenser fans thermal protection
Automatic
OFF
-
OFF
OFF
A61
Maximum service hours for
compressor 1 exceeded
Notification
-
-
-
-
AC1
Compressor 1 thermal protection
Manual
OFF
-
-
-
AE1
Anti-freeze
Power shut-off
OFF
ON
-
ON
AH0
General high water pressure
Manual
OFF
-
-
-
AP0
General evaporator pump
Manual
OFF
OFF
OFF
OFF
AP1
Thermal protection water pump 1
Automatic
-
OFF
-
-
A13
Maximum anti-frost time exceeded
Notification
-
-
-
-
AL0
General low water pressure
protection
3 times within 1 hour
OFF
-
-
-
A50
General fan thermal protection
Automatic
OFF
-
OFF
-
A7A
Intake water probe
Automatic
OFF
OFF
OFF
OFF
A7B
Outlet water probe
Automatic
OFF
OFF
OFF
OFF
A7V
Intake transducer probe
Automatic
OFF
OFF
OFF
OFF
A7G
Discharge tansducer probe
Automatic
OFF
OFF
OFF
OFF