12
AIR COOLED WATER CHILLERS
– AXIAL FANS
EKWXA/EKWXBA
11.15 207443 Rev104
• It is advisable to examine carefully the unit upon receipt.
• Inspect equipment received for damage or missing element. If units are damaged or shipment is
incomplete, immediately file the claim with the transport company. (Within the first 48h)
• Check if unit nameplate voltage is correct and agrees with local power supply.
• In case of detecting any damage or anomaly it is recommended to contact our customer support.
If the unit is to be stored before installation, several precautions must be kept to avoid any damages,
corrosion or any other type of deterioration:
• Do not store the unit in locations with temperatures over 50ºC and preferably without exposure to direct
sunlight.
• Minimum storage temperature: -10ºC
• Maximum humidity: 90%
Moreover it is recommended:
- Move it carefully
- Avoid placing other objects on the unit (Unless this is done within the overlay limits indicated in the
packaging)
- Avoid placing the unit with heat shrink protection under the sun, as the pressure of the circuits might
assume values that could lead to activation of the safety valves
• Before moving the unit be sure that all units panels are well fixed.
• Raise and set down the equipment carefully.
• Never tilt the unit more than 15 degrees during transportation (Fig. 2).
• When lifting the unit ensure that it is balanced and steady, keep in mind that the heaviest part is where
the compressor is installed.
• Always transport unit to installation place in original packaging.
RIGGING
STORAGE
INSPECTION UPON ARRIVAL
UNIT RECEPTION