17
IOM_CCHIBA-CSTIBA_301_207925_170706_EN
CCHIBA/CSTIBA
SPLIT HORIZONTAL INVERTER UNITS
PACKAGED AIR-AIR
REFRIGERANT LINES
For more information on the dimensioning of the refrigeration lines, request document with reference 207682 Rev100.
COOLING CIRCUIT
Split systems demand a correct disposition of refrigerant piping and a correct connection between both indoor and outdoor
units.
Pressure drop of the line
Circulation speed of the refrigerant
Refrigerant mass
DISCHARGE LINES
In heat pump operation, the low pressure line works as high pressure line.
LINES POSITION
1. When indoor unit is at a lower level than outdoor unit:
It is not essential to install traps in the vertical line. However, it could be convenient to install some every 6 to 9 meters
in order to help oil return.
When working with the machines in operation, discharge line temperature is
very HIGH and could hurt people.