13
IOM_CCHIBA-CSTIBA_301_207925_170706_EN
CCHIBA/CSTIBA
SPLIT HORIZONTAL INVERTER UNITS
PACKAGED AIR-AIR
TECHNICAL DATA
(1) Cooling Rated Conditions:
Internal temperature DB: 27ºC, Internal temperatura WB: 19ºC
(2) Heating Rated Conditions:
Internal temperature DB: 20ºC
(3) GWP:
Global warming potential (climatic) of 1 kg of greenhouse gas relative to 1 kg of CO
2
, calculated
in terms of 100-year warming potential.
(4)
Just the units which has serial “FLARE” (not from option) are charged with refrigerant, the rest come
pre-charged with dry nitrogen to prevent the emtry of moisture.
CCHIBA
301
CAPACITIES
Rated Cooling Capacity (1)
KW
7.4
Cooling Capacity (20
– 100 – 120 Hz)
KW
1.2
– 7.4 – 8.1
Rated Heating Capacity (2)
KW
7.5
Heating Capacity (20
– 100 – 120 Hz)
KW
1.3
– 7.5 – 8.3
Coeficient EER
>8
SEER
4.6
Class
B
SCOP (Warm Zone)
4.1
Class
A+
Sound Power
dBA
70
REFRIGERANT
Type
R-410A
Global Warming Potential (GWP) (3)
2088
Number of Refrigerant Circuits
1
Frigorific Connection Liquid Line
“
3/8
Frigorific Connection Gas Line
“
1/2
Charge (Include 0 m of Lines) (4)
Kg
2.7
COMPRESSOR
Type
BRUSHLESS DC MOTOR
Number
2
Oil type
Ester VG74
Oil Volume
L
0.65
INDOOR HEAT EXCHANGER
Type
Aluminum Fins and Copper Pipes
Frontal Surface
m
2
0.372
Fins Size
mm
1.8
Piping Diameter
"
5/16
ELECTRICAL SPECIFCATIONS
Power Supply
V / phases /
Hz
220-240 / I / 50
Electric Connections
mm²
2 x 2.5 + T
Interconnection Between Units
Twisted Pair + Shielded
OUTDOOR FAN
Type
Centrifugal with Double Suction
Model
10/10 DD
Voltage
V
230/1/50
Motor Power
KW
0.55
Transmission
Integrated in Motor
Rated Airflow
m3/h
2600
Maximum Airflow
m3/h
3000
Available Static Pressure
Pa
50
Maximum Speed Fan
R.P.M.
1014
DIMENSIONS AND WEIGHT
Length
mm
1445
Width
mm
825
Height
mm
504
Weight
Kg
150