WHAT TO DO IF... 

 

 

There is little outflowing air

 

Possible cause: 

incorrect speed setting on the control panel 

Possible remedy: 

select the right speed

 

Possible cause: 

clogged filter

 

Possible remedy: 

clean the filter

 

Possible cause: 

obstruction of the airflow on the intake or delivery

 

line

 

Possible remedy: 

remove obstruction

 

The motor does not turn? Check that…

 

... the power supply is switched on

 

... the switches or thermostats are in the correct 

operating position

 

... there is no foreign matter jamming the rotation of 

the fan

 

The unit does not heat/cool as before? Check that…

 

... the filter and the coil are clean

 

... no air has entered the water circuit by bleeding from 

the relative valve

 

... the installation is correctly balanced

 

... the boiler/chiller is in proper working order

 

 

DISMANTLING THE UNIT 

 

This  unit  is  made  to  last  for  many  years.  Qualified  personnel  are  needed  to 

dismantle it in all safety. The first operation to be carried out before dismantling 

the unit is to disconnect it once and for all from the electricity supply.

 

This unit has been made using recyclable materials (copper, aluminum, brass, 

plastic) and assembled by screws and push-fits to make separation of the parts 

easy.

 

Contact a firm specialized in differentiated waste disposal; it is the only way   to 

be  certain  of  correct  recycling  and  thereby  contribute  to  protection  of  the 

environment.

 

 

Содержание BSW 1

Страница 1: ...Rev 102 1 BSW Cooling only FAN COIL HIGH PRESSURE Models 1 2 3 4 5 6 7 Cooling capacities from 3 8 to 50 6 kW Heating capacities from 5 0 to 60 9 kW 06 18 Ref 207483 Rev 102 INSTALLATION OPERATION AND MAINTENANCE MANUAL ...

Страница 2: ...BSW FAN COIL HIGH PRESSURE 2 06 18 Ref 207483 Rev 102 ...

Страница 3: ...LY DIAGRAM 10 PAM MOUNTING BRACKET ASSEMBLY DIAGRAM 11 RAM MOUNTING BRACKET ASSEMBLY DIAGRAM 11 GAM ASSEMBLY DIAGRAM 12 SRE ASSEMBLY DIAGRAM 12 SRA ASSEMBLY DIAGRAM 13 USG ASSEMBLY DIAGRAM 13 SSP ASSEMBLY DIAGRAM 14 ALUMINIUM DAMPER ASSEMBLY DIAGRAM 14 BAM ON PAN ASSEMBLY DIAGRAM 15 BAM ON RAM ASSEMBLY DIAGRAM 15 SUPPLY GRILL ON PAM ASSEMBLY DIAGRAM 16 SUPPLY GRILL ON RAM ASSEMBLY DIAGRAM 16 INTAK...

Страница 4: ...ed for long periods make sure that the controls are in the position 0 off If the unit is not going to be used in winter when temperatures are near to freezing drain the system and ensure that the unit heat exchanger has no water in it in order to prevent the formation of ice and consequent breakage To make the unit inoperable disconnect it totally from the electricity supply It is unsafe to alter ...

Страница 5: ... 656 956 1156 1306 1406 B mm 253 253 303 328 353 M mm 680 980 1180 1330 1430 C mm 247 247 297 322 347 D mm 237 237 237 300 5 300 5 E mm 118 118 118 195 195 F mm 93 5 93 5 118 5 131 143 5 G mm 233 233 233 310 310 I mm 83 5 83 5 108 5 121 133 5 N mm 193 193 193 270 270 Fittings male 2 rows coil Ø 1 2 1 2 3 4 3 4 1 4 rows coil Ø 1 2 3 4 3 4 1 1 6 rows coil Ø 3 4 3 4 1 1 1 1 4 Net weight kg 28 38 49 6...

Страница 6: ...7 MOD 6 7 L mm 2190 2190 H mm 373 398 P mm 770 770 A mm 2076 2076 B mm 328 353 M mm 2100 2100 C mm 323 348 D mm 300 5 300 5 E mm 201 5 201 5 F mm 131 5 144 G mm 311 311 I mm 121 5 134 N mm 270 270 Fittings male 2 rows coil Ø 1 1 4 rows coil Ø 1 1 4 1 1 2 6 rows coil Ø 1 1 2 1 1 2 Net weight kg 127 Pic 02 ...

Страница 7: ...ply line Drill the holes in line with the relative slots for the 6 unit screw anchors Pic 4 Inject thermosetting resin into the holes and then insert the screw anchors Pic 5 Fix the threaded rods of the correct length to the screw anchors Pic 5 and insert them into the relative slots Pic 6 After having created a slope max 3 cm m in the direction of the condensate outlet lock the threaded rod with ...

Страница 8: ...8 Ref 207483 Rev 102 EXAMPLE OF ACCESSORIES USE AND COMPATIBILITY UNIT PAM RAM GAM SRE SRA USG SSP Aluminium damper BAM Air intake grill Air supply grill Depending on the requirements the air filter can have a thickness of 12 25 48 mm ...

Страница 9: ...LENUM ASSEMBLYDIAGRAM PAM INTAKEPLENUM ASSEMBLYDIAGRAM SCREWS LEGEND PAM 1 5 x8 Screw TC M5x12 UNI7687 x6 Hex nut M5 flanged with corrugated washer DIN4161 SCREWS LEGEND PAM 6 7 x10 Screw TC M5x12 UNI7687 x6 Hex nut M5 flangiato with corrugated washer DIN4161 Pic 07 ...

Страница 10: ...TE M5x12 UNI 5739 TE M5x12 SCREWS LEGEND RAM 6 7 x6 Screw TC M5x12 UNI7687 x6 Hex nut M5 flanged with corrugated washer DIN4161 x4 Screw TE M5x12 UNI 5739 Pic 09 SCREWS LEGEND RAM 1 5 x7 Screw TC M5x12 UNI7687 TE M5x12 x6 Hex nut M5 flanged with corrugated washer DIN4161 x1 Screw TE M5x12 UNI 5739 SCREWS LEGEND RAM 6 7 x8 Screw TC M5x12 UNI7687 x6 Hex nut M5 flanged with corrugated washer DIN4161 ...

Страница 11: ... 207483 Rev 102 11 PAMMOUNTINGBRACKETASSEMBLYDIAGRAM RAMMOUNTINGBRACKETASSEMBLYDIAGRAM SCREWS LEGEND 1 5 x6 Self drilling screw with tip TC 3 9x9 5 UNI6954 Pic 11 SCREWS LEGEND 1 5 x6 Self drilling screw with tip TC 3 9x9 5 UNI6954 Pic 12 ...

Страница 12: ... 102 GAMASSEMBLYDIAGRAM SREASSEMBLYDIAGRAM SCREWS LEGEND SRE 1 5 x8 Screw TC M5x12 UNI7687 x6 Hex nut M5 flanged with corrugated washer DIN4161 SCREWS LEGEND SRE 6 7 x10 Screw TC M5x12 UNI7687 x6 Hex nut M5 flanged with corrugated washer DIN4161 Pic 14 ...

Страница 13: ...2 13 SRAASSEMBLYDIAGRAM USGASSEMBLYDIAGRAM SCREWS LEGEND SRA 1 5 x8 Screw TC M5x12 UNI7687 x6 Hex nut M5 flanged with corrugated washer DIN4161 SCREWS LEGEND SRA 6 7 x10 Screw TC M5x12 UNI7687 x6 Hex nut M5 flanged with corrugated washer DIN4161 Pic 15 ...

Страница 14: ...AGRAM CANALIZABLE SIDE Lined up to the edge SCREWS LEGEND SSP 1 5 x8 Screw TC M5x12 UNI7687 x6 Hex nut M5 flanged with corrugated washer DIN4161 UNIT ACCESSORIES SIDE Shorter to mix the air flow SCREWS LEGEND SSP 6 7 x10 Screw TC M5x12 UNI7687 x6 Hex nut M5 flanged with corrugated washer DIN4161 Pic 17 ...

Страница 15: ... BAM ON PANASSEMBLYDIAGRAM BAM ON RAMASSEMBLYDIAGRAM SCREWS LEGEND 1 5 x8 Screw TC M5x12 UNI7687 x8 Hex nut M5 flanged with corrugated washer DIN4161 SCREWS LEGEND 6 7 x10 Screw TC M5x12 UNI7687 x10 Hex nut M5 flanged with corrugated washer DIN4161 Pic 19 ...

Страница 16: ...RAM SUPPLYGRILLON RAMASSEMBLYDIAGRAM SCREWS LEGEND 1 5 x6 Self drilling screw TC 4 2x13 UNI8118 SCREWS LEGEND 6 7 x8 Self drilling screw TC 4 2x13 UNI8118 Pic 21 SCREWS LEGEND 1 5 x6 Self drilling screw TC 4 2x13 UNI8118 SCREWS LEGEND 6 7 x8 Self drilling screw TC 4 2x13 UNI8118 Pic 22 ...

Страница 17: ...RAM INTAKE GRILL ON RAMASSEMBLYDIAGRAM SCREWS LEGEND 1 5 x6 Self drilling screw TC 4 2x13 UNI8118 SCREWS LEGEND 6 7 x8 Self drilling screw TC 4 2x13 UNI8118 Pic 23 SCREWS LEGEND 1 5 x6 Self drilling screw TC 4 2x13 UNI8118 SCREWS LEGEND 6 7 x8 Self drilling screw TC 4 2x13 UNI8118 Pic 24 ...

Страница 18: ... of the water in the trap Upon completion of work check that the condensate flows out properly by pouring water into the tray The condensate water drainage system should be fabricated in a workmanlike manner and should be periodicallychecked The manufacturer cannot be held liable for any damage caused by dripping in the absence of a valve or of periodic maintenance of the drainage system ELECTRICA...

Страница 19: ...BSW FAN COIL HIGH PRESSURE 06 18 Ref 207483 Rev 102 19 WIRING DIAGRAM MOD 1 3 ...

Страница 20: ...BSW FAN COIL HIGH PRESSURE 20 06 18 Ref 207483 Rev 102 WIRING DIAGRAM MOD 4 5 ...

Страница 21: ...BSW FAN COIL HIGH PRESSURE 06 18 Ref 207483 Rev 102 21 WIRING DIAGRAM MOD 6 7 ...

Страница 22: ...ND MAINTENANCE CAUTION Before carrying out any cleaning or maintenance work disconnect the unit from the mains electricity supply ROUTINE MAINTENANCE The user is duty bound to have all maintenance operations carried out by trai ned and qualified personnel only If the unit has to be dismantled protect hands with work gloves Monthly checks Ensure that the fan impellers are clean If they are dirty cl...

Страница 23: ...as before Check that the filter and the coil are clean no air has entered the water circuit by bleeding from the relative valve the installation is correctly balanced the boiler chiller is in proper working order DISMANTLING THE UNIT This unit is made to last for many years Qualified personnel are needed to dismantle it in all safety The first operation to be carried out before dismantling the uni...

Страница 24: ...BSW FAN COIL HIGH PRESSURE 24 06 18 Ref 207483 Rev 102 NOTES ...

Страница 25: ... 18 Ref 207483 Rev 102 25 HIPLUS AIRE ACONDICIONADO S L Masia Torrents 2 Tel 34 93 893 49 12 Fax 34 93 893 96 15 08800 Vilanova i la Geltrú Barcelona Spain www hitecsa com We reserve the right to change specification without notice ...

Отзывы: