º
8
IOM_ACVBA-ACVA_351a2402_207958_180109_EN
ACVBA-ACVA
PACKAGED VERTICAL COMPACT UNITS
AIR-AIR
TECHNICAL SPECIFICATIONS
MODEL
351
401
501
701
721
CAPACITIES
Cooling capacity
kW
9.8
12.5
14.4
18.9
19.6
Heat capacity
kW
10.4
13.7
15
20
21
EER Coefficient
2.2
2.2
2
2.3
2.1
COP Coefficient
2.5
2.7
2.3
2.6
2.6
Number of refrigerating circuits
1
1
1
1
1
REFRIGERANT
Type
R410A
GWP (1)
2088
Load (2)
3.5
4.2
4
6.2
5.8
COMPRESSOR
Type
Rotational
Scroll
Scroll
Scroll
Scroll
Number
1
1
1
1
1
Oil type
PVE
PVE
PVE
PVE
POE
Oil volume
l
1.3
1.7
1.7
1.7
2.8
Type
FV60S
FV68S
FV68S
FV68S
FV68S
OUTDOOR CIRCUIT FAN
Type
Centrifugal, double aspiration
Nominal air flow
m
3
/h
4300
3950
4900
6800
6800
Available static pressure
Pa
50
50
50
50
50
Model
10/10 SS
12/12 SS
12/12 SS
15/15 SS
15/15 SS
Power
kW
0.75
0.55
0.75
1.1
1.1
Speed
r.p.m.
1083
825
829
746
746
INDOOR CIRCUIT FAN
Type
Centrifugal, double aspiration
Nominal air flow
m
3
/h
2315
2600
3540
4720
4720
Available static pressure
Pa
43
50
60
55
55
Model
10/10 DD
10/10 DD
10/10 SS
12/12 SS
12/12 SS
Power
kW
0.25
0.55
0.55
0.75
0.75
Speed
r.p.m.
872
870
1032
809
809
DIMENSIONS AND WEIGHT
Length
mm
937
937
1087
1130
1130
Width
mm
750
750
750
800
800
Height
mm
1603
1603
1603
1900
1900
Weight
kg
251
276
290
367
392
1.
GWP: Global Warming Potential (climatic) of 1 kg of greenhouse gas relative to 1 kg of CO2, calculated in terms of 100-year
warming potential.
2.
Only units with “FLARE” valve as standard (not option) are loaded with refrigerant, the rest of them are loaded with dry nitrogen
to prevent the entry of moisture.