“B” Function
Defaults
Func.
Code
Name /
SRW Display
Description
Run
Mode
Edit
-FE
(EU)
-FU
(USA)
Units
Selection of controlled stop
operation
B050
IPS MODE
OFF
Two option codes:
00
}
Disabled
01
}
Enabled (stop)
02
}
Enabled (restart)
U
00
00
Controlled stop operation
start voltage setting
B051
IPS V
0000.0V
Setting of DC bus voltage to start
controlled stop operation. Range
is 0.0 to 1000.0
U
0.0
0.0
V
OV-LAD Stop level of
controlled stop operation
setting
B052
IPS OV
0000.0V
Setting the OV-LAD stop level of
controlled stop operation. Range
is 0.0 to 1000.0
U
0.0
0.0
V
Deceleration time of
controlled stop operation
setting
B053
IPS DEC
0001.0s
Range is 0.01 to 3000
U
1.0
1.0
sec
Frequency drop for quick
deceleration setting
B054
IPS F
0000.0Hz
Setting of the first quick drop in
frequency. Range is 0.0 to 10.0
U
0.0
0.0
Hz