• For the CBLM/CBLH, push the power supply units all the way into their
slots and tighten using the blue screws. If the power cables connected
to the target power supply units are loose, push the plugs of the
power cables into the sockets of the power supply units to connect the
cables securely.
4.
Log out of the maintenance utility to close the window.
Replacing a power supply for SFF and LFF drive trays
Caution:
Be sure to replace the faulty power supply. If you replace the
operational power supply, the system will go down.
Caution:
A short-circuit can cause a fire. Never insert metal or other objects
into the cable connector; otherwise, a short-circuit can occur.
Note:
Power supply unit #1 and power supply unit #2 are installed in
opposite directions.
Before you begin
• Wear a wrist strap connected to the storage system to prevent part
failures caused by static electricity. Do not remove the wrist strap until you
finish the procedure.
• Confirm that the storage system power is turned on.
• Confirm that the red
ALM
LED for the power supply unit to be replaced is
on.
148
Replacing a power supply
Service Guide for VSP Gx00 and VSP Fx00 Models
Содержание Virtual Storage Platform F400
Страница 4: ...4 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 22: ...22 Preface Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 106: ...106 Replacing storage system components Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 140: ...140 Replacing a fan Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 146: ... CBLM CBLH 146 Replacing a power supply Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 160: ...160 Replacing a power supply Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 198: ...6 Click Block 198 Replacing cache memory Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 222: ...222 Replacing a small form factor pluggable SFP Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 250: ...250 Replacing a SAS cable Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 260: ...260 Replacing cache flash memory Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 268: ...268 Replacing a LAN blade Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 278: ...278 Replacing a backup module Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 284: ...284 Replacing a PCIe module Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 296: ...296 Replacing a PCIe cable connector Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 302: ...302 Replacing a PCIe cable Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 312: ...312 General maintenance Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 395: ...CBSS CBSSD controller Warning labels on the storage system 395 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 396: ...CBSL CBSLD controller 396 Warning labels on the storage system Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 397: ...Warning labels on the storage system 397 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 398: ...CBLM controller CBLH controller 398 Warning labels on the storage system Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 401: ...Flash module drive tray Warning labels on the storage system 401 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 402: ...Dense intermix drive tray 402 Warning labels on the storage system Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 405: ...Warning labels on the storage system 405 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 410: ...PCIe switch board 410 Warning labels on the storage system Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 411: ...NAS module Warning labels on the storage system 411 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 412: ...412 Warning labels on the storage system Service Guide for VSP Gx00 and VSP Fx00 Models ...
Страница 417: ...Service Guide for VSP Gx00 and VSP Fx00 Models ...