4 . 2 General Current Test
The general current test requires assembly of a test rig consisting of a power supply or
Variac (for AC voltage control), a high impedance voltmeter, a 100 ohm/10 watt resistor
and an ammeter calibrated to read in milliamperes. The test rig is assembled as shown
in Figure 4-1. The test may be conducted with the cover on or off the case.
U
S0
10
5.
00
03
.0
0
POWER
SUPPLY
OR
VARIAC
AMMETER
100 OHM/10 WATT
RESISTOR
A
V
HIGH IMPEDANCE
VOLTMETER
TERMINAL
2
TERMINAL
1
USSP
Figure 4-1. USSP Test Set Up
Use Table 4-1 to select the proper input voltage for the particular USSP model being
tested. Apply this voltage to terminals 1 and 2.
NOTE
If applied voltage is DC, apply "Plus" to terminal 2 and
"Minus" to terminal 1.
For the selected voltage setting (corresponding to the "Maximum Circuit" rating of the
unit), the ammeter should show a current equal to or less than that indicated in column
3 of Table 4-1. If the ammeter indicates a higher current, the unit should be replaced.
Содержание SM 6145
Страница 2: ...STS USASecondary Surge Suppressors USSP Copyright 2019 SM 6145 Rev 3 March 2019 ...
Страница 6: ...STS USASecondary Surge Suppressors USSP Copyright SM 6145 Rev 23 March 2019 iv ...
Страница 12: ...STS USASecondary Surge Suppressors USSP Copyright SM 6145 Rev 23 March 2019 1 6 ...
Страница 14: ...STS USASecondary Surge Suppressors USSP Copyright SM 6145 Rev 23 March 2019 2 2 ...
Страница 20: ...STS USASecondary Surge Suppressors USSP Copyright SM 6145 Rev 23 March 2019 4 4 ...
Страница 24: ...STS USASecondary Surge Suppressors USSP Copyright SM 6145 Rev 23 March 2019 5 4 ...
Страница 26: ...STS USASecondary Surge Suppressors USSP Copyright SM 6145 Rev 23 March 2019 6 2 End of Manual ...