Chapter 3
Operation
3-17
3.5 Basic Parameter Setting to Drive Motor
3.5.1 Setting Frequency command source and Run command source
This section describes how to drive the motor with SJ700D briefly.
The frequency and run command are necessary to drive the motor with the inverter.
In many cases, these sources are set as below;
Setting the frequency
:
(A) Data settings (Digital operator)
(B) Via external analog signals (Control terminal)
Run and stop
:
(A) RUN / STOP key (Digital operator)
(B) Via external signal (Control terminal)
The frequency command and Run command sources can be changed by the parameter A001 (Frequency command
source) and A002 (Run command source) respectively.
In addition to the basic setting mentioned above, there are several options for A001 and A002 setting.
Parameter
Detail
Data range
Initial settings
****FF3
****FEF3
****FUF3
A001
Frequency source
00(keypad potentiometer)
01(control circuit terminal block)
02(operator)
03(RS485)
04(option 1)
05(option 2)
06(pulse-string input)
07(easy sequence)
10(operation function result)
02
01
A002
Run command source
01(control circuit terminal block)
02(operator)
03(RS485)
04(option 1)
05(option 2)
02
01
*) This chapter explains 01(control circuit terminal block) and 02(operator) mainly.
Содержание SJ700D-004L
Страница 16: ...Contents Appendix Appendix A 1 Index Index Index 1 ...
Страница 44: ...Chapter 2 Installation and Wiring 2 23 Memo ...
Страница 70: ...Chapter 3 Operation 3 25 Memo ...
Страница 248: ...Chapter 5 Error Codes 5 11 Memo ...
Страница 256: ...Chapter6 Maintenance and Inspection 6 7 Memo ...
Страница 282: ...Chapter 8 List of Data Settings 8 17 Memo ...